S e c t i o n 9 : E n t r y a n d E x i t D e l a y
Upon arming, the panel will begin the Exit Delay
the exit delay expires (see 9.2 'Entry and Exit Delay Options'). The keypad will beep rapidly for the last 10 seconds of the exit delay
to warn the user that the system is about to arm.
Upon entry, if a Delay type zone is violated, the panel will begin an Entry Delay
will pulse the sounder during the last 10 seconds of the entry delay to warn the user that the system is about to go into alarm.
You can turn off the entry and/or exit delay tones at each keypad. See 6.3 'Keypad Toggle Options'.

9.1 Entry and Exit Delay Times

Ref #: [0100XX02] where XX = Partition 01-08
The entry and exit delay times are programmed for each
partition. These times will program the length of each
delay. Entry Delay, Exit Delay, Auxiliary Entry Delay and
Auxiliary Exit Delay. Three digits are required for each
entry. The times are programmable from 000 to 255 seconds.
The four partition times are as follows:
• Entry Delay
Entry Delay
Entry Delay
Entry Delay - The entry delay will begin when a delay
type zone is violated (Default = 30 seconds).
• Exit Delay
Exit Delay
Exit Delay
Exit Delay - The exit delay will begin when a valid
access code is entered to arm the partition (Default = 120
seconds).
• Auxiliary Entry Delay
Auxiliary Entry Delay
Auxiliary Entry Delay
Auxiliary Entry Delay - This entry delay will begin
when an Auxiliary Delay zone is violated. This delay
time must be greater than the standard Entry Delay
(Default = 45 seconds).
• Auxiliary Exit Delay
Auxiliary Exit Delay - This exit delay is for Auxiliary
Auxiliary Exit Delay
Auxiliary Exit Delay
Delay zones. This delay time must be greater than the
standard Exit Delay (Default = 120 seconds).

9.2 Entry and Exit Delay Options

Ref # [0100XX01] where XX = Partition 01-08
The following exit and entry delay options will determine
how the delays will sound. These options are programmed
by partition.
• Exit Delay Aud
Exit Delay Aud - If enabled, the keypad will beep during
Exit Delay Aud
Exit Delay Aud
the exit delay (once per second; twice per second during
the last 10 seconds of the delay). If disabled, the keypad
will be silent during the exit delay (default=No).
• Exit Delay Sqk
Exit Delay Sqk - If enabled, the burg bell outputs will
Exit Delay Sqk
Exit Delay Sqk
activate during the exit delay (once per second; twice
per second during the last 10 seconds of the delay). If
disabled, the outputs will be silent during the exit delay.
• Entry Urgency
Entry Urgency - If enabled, the keypad will beep three
Entry Urgency
Entry Urgency
times every second during the last 10 seconds of the
entry delay (default=No).
• Entry Squawk
Entry Squawk
Entry Squawk
Entry Squawk - If enabled, the burg bell outputs will
sound during the entry delay (once per second; twice
per second during the last 10 seconds of the delay). If
disabled, the outputs will be silent during the entry
delay (default=No).
• Exit Del. Term.
Exit Del. Term.
Exit Del. Term.
Exit Del. Term. - If enabled, the exit delay will reduce to
five seconds if a Standard Delay zone is opened and
closed during the delay period. The bell squawk and
keypad notification will cease upon the restoral of the
delay zone. At the end of the delay, the partition will be
armed (default=No).
NOTE: The exit delay termination time will be extended
to eight seconds for systems with AML loops (over 32
detectors).
• Spcl Alm Entry
Spcl Alm Entry - If enabled, the panel will sound an
Spcl Alm Entry
Spcl Alm Entry
alternate entry delay if an alarm memory is present: The
keypad sounders will pulse to indicate an alarm in
memory. If disabled, the panel will sound the normal
entry delay, even if an alarm has occurred during the
armed period (default=Yes).
30
Exit Delay. If the 'Exit Delay Aud' option is enabled, the keypad will beep every second until
Exit Delay
Exit Delay
Entry Delay. The keypad will emit a steady tone. The keypad
Entry Delay
Entry Delay
• Exit Tbl Beep
Exit Tbl Beep - If enabled, when the system is armed
Exit Tbl Beep
Exit Tbl Beep
with any trouble present, the keypad will sound a series
of 12 beeps before the exit delay begins. If disabled,
there will be no warning beeps when arming to indicate
a trouble condition (default=No).
NOTE: If AC Trouble displayed is disabled the annunciation
will not occur for AC Trouble.
• Push to Set
Push to Set - If a Push to Set zone is assigned to the par-
Push to Set
Push to Set
tition the exit delay will not be completed until the Push
to Set zone is tripped.
• Extended Exit Delay
Extended Exit Delay
Extended Exit Delay - If the exit delay is programmed
Extended Exit Delay
for 255 seconds then the exit delay will count down nor-
mally. It will not expire until a delay zone assigned to
the partition is opened and closed.
Note that the exit delay termination feature must be
enabled and a standard delay zone must be assigned to
the partition.
NOTE: Do not use this feature with the PC4820 Door Shunt
feature.