• Other types of zones may also be assigned to this parti-
tion without effecting the fire operation as described
below.
Operation
On alarm, from any fire zone in this partition, the fire auto-
scroll display will only show on keypads assigned to the
fire partition and on any system global keypads.
The waterflow and 2-wire smoke zones on the PC4701
module will show, in the auto-scroll mode, on all partition
and global keypads. If a zone on the PC4701 is in alarm,
then fire silence and reset can be done from any partition
keypad.
If the alarm is from a partition zone (not PC4701) then fire
alarm silence and reset can only be done directly on the fire
partition keypad(s). To silence from other partition keypads
or a global keypad requires that the keypad be loaned to the
fire partition.
Fire Configuration 2 (Recommended)
• Assign ALL fire zones to ALL active partitions in the
system. Do not program fire zones as 'silent'.
• PC4702 Bell zones automatically respond to any fire
zone in the system and can be assigned to any partition.
• Zones on the PC4701 module are always global and do
not require partition assignment.
• One or more fire keypads may be located on any parti-
tion.
Operation
On alarm, the fire auto-scroll display will show on all parti-
tion keypads and on all global keypads.
Fire alarm silence and fire system reset may be done
directly on any partition keypad. To silence from a global
keypad requires that the global keypad be loaned to one of
the partitions.
NOTE: Assign command output 2 (sensor reset) to all parti-
tions.
55