S e c t i o n 2 1 : L i s t i n g R e q u i re m e n t s
21.1 UL Listed Commercial Burglary and Resi-
dential Burglary/Fire Installations
The installation requirements listed below must be met for
the following grades of service.
Grade AA Central Station and Police Connect
The installation must use T-Link module which communi-
cates over LAN/WAN to the Sur-Gard MLR-IP receiver.
Polling time must be 90 seconds. Compromise detection
time must be 6 minutes.
Grade A Local
The installation must have a bell UL Listed for mercantile
local alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade B Central Station and Grade A Police Connect
The installation must have a bell UL Listed for mercantile
local alarms (AMSECO MBL10B).
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
Grade C Central Station
The digital communicator must be enabled.
The control panel must be in the Attack Resistant Enclosure
(UL Listed DSC models CMC-1, PC4004C, PC4050CAR/or
PC4050CRAR).
All Commercial Installations
The entry delay must not exceed 60 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cutoff time is 15 minutes.
Residential Installations
The entry delay must not exceed 45 seconds
The exit delay must not exceed 60 seconds.
The minimum bell cut-off time is 4 minutes.
Programming
The notes in the programming sections describing the sys-
tem configurations for UL Listed installations must be
implemented.
Control of the Protected Premises
In order to have a UL Certificated system the protected area
is to be under the responsibility of one ownership and man-
agement (i.e. one business under one name). This may be a
group of buildings attached or unattached with different
addresses but under the responsibility of someone having
mutual interest. The person of mutual interest is not the
alarm installing company.
Bell Location
The alarm sounding device (bell) must be located where it
can be heard by the person or persons responsible for main-
taining the security system during the daily arming cycle.
Protection of the Control Unit
The local control and the local power supply must be pro-
tected by one of the following ways:
• The control unit and audible alarm device must be in a
protected area which is armed 24 hours a day.
• Each partition shall arm the area protecting the control
unit and the audible alarm device power supply. This
may require duplicate protection armed by each parti-
tion. Access to this protected area, without causing an
alarm, will require that all partitions be disarmed.
In all cases described above, the protected area for the con-
trol unit must be programmed as not bypassable.
Casual Users
The installer should caution the user(s) to not give system
information to casual users (e.g. codes, bypass methods,
etc. to baby-sitters or service people). Only the One-Time
Use codes should be given to casual users.
User Information
The installer should advise the users and note in the user
instruction manual:
• Service organization name and telephone number
• The programmed exit time
• The programmed entry time

21.2 Commercial Fire Alarm Installations

System Specifications
• Class B / Style B 2-Wire Smoke Detector Supervision
• Class B/ Style B Waterflow Supervision
• Notification Appliance Circuit Supervision
• Service Type: Automatic, Manual, Sprinkler Supervi-
sory, Waterflow
• Signaling Type: Non-coded
• Ground Fault Supervision
• Supervised Dual Telephone Lines
PC4XXX modules other than those specified have not been
investigated by UL for use with commercial fire alarm sys-
tems and cannot be used for commercial fire service.
All other modules providing burglary sevice must be pro-
vided in a separate enclosure.
2-Wire Smoke Detector Compatibility
• Maximum loop resistance: 100 ohms
• Operating Voltage Range: 8.9 - 12.0
• Maximum Alarm Current: 80 mA
• Compatibility Identifier: FM-2
• The following 2-wire smoke detectors are compatible
with the PC4020CF/PC4701:
Manufacturer
Model
DSC
MN-220
DSC
MN-220T
System Sensor
1100
System Sensor
2100D
System Sensor
2100T
System Sensor
2400
System Sensor
1400
System Sensor
1151
System Sensor
2151
1151
System Sensor
System Sensor
2151
System Sensor
1451
System Sensor
1451
DSC
FSA-210B
Base
Type
None
Photo
None
Photo w/ heat
None
Ion
None
Photo
None
Photo w/ heat
None
Photo
None
Ion
B401
Ion
B401
Photo
B110LP
Ion
B110LP
Photo
B401
Ion
B401B
Ion
None
Photo
61