1.1 The CFP-102
Fire Alarm
Control Unit
1.2 Codes, Standards
and Installation
Requirements

Section 1: Introduction

1.1.1 General features
Two initiating device circuits, class B / style B
Two notification appliance circuits, class B / style Y (Power Limited)
[can be wired as one NAC, class A / style Z]
One common alarm-actuated relay, form 'C'
One common trouble-actuated relay, form 'C'
AUX+ power output, 500 mA max. (Power Limited)
Unswitched common and switched common auxiliary power returns
Integral battery charger
Cabinet with dead-front construction
Transformer, mounted in the cabinet
1.1.2 Applications
The CFP-102 two zone, fire alarm control panel is listed for use in the following applications.
Protected Premises Fire Alarm System
And for the following types of service:
A – automatic, M – Manual, SS – Sprinkler Supervisory, WF – Waterflow
1.2.1 Relevant codes and standards
The CFP-102 fire alarm control panel is designed to meet the requirements of NFPA 72, 1996
edition, UL 864, Control Units for Fire Protective Systems, 1996 edition and in Canada, CAN/
ULC-S527, Standard for Control Units for Fire Alarm Systems, 1999 edition.
Information provided with this unit is intended as a guide. Installation of this equipment,
optional system components, alarm initiating devices and notification appliances must follow
the manufacturer's guidelines as contained in their respective installation documents, all appli-
cable codes and the instructions of the Local Authority Having Jurisdiction.
1.2.2 General Installation requirements
Manufacturer's documents:
When installing the CFP-102 control panel, refer to this manual. When installing optional sys-
tem components refer to the installation documents included with those components. When
installing compatible alarm initiating devices or notification appliances, refer to the installation
documents included with those products.
Field wiring:
Field wiring recommendations in this document are intended as guidelines. All field wiring
must be installed in accordance with NFPA 70 National Electrical Code and in Canada with
the standard for installation ULC/S 524, the most current Canadian Electrical Code, with all
relevant local codes and standards, and the Authority Having Jurisdiction.
Compatible devices:
Use UL or ULC Listed smoke detectors and notification appliances that are compatible with
the CFP-102 Fire alarm control panel from the lists included in this manual.
Smoke detector alarm verification:
The CFP-102 alarm initiating zones can be configured for 'Alarm Verification'. If this feature is
used then do not use smoke detectors with built-in Alarm Verification.
NOTE: Use of alarm verification may require the approval of the local AHJ.