Operating Guide | VLT® Decentral Drive FCD 302
7 Specifications
7.1 Electrical Data
Table 17: Shaft Output, Output Current, and Input Current
Mains supply 3x380–480 V AC
Drive
Rated shaft output [kW]
Rated shaft output [hp]
Maximum input current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Recommended maximum fuse size (non-UL)
Built-in circuit breaker (large unit)
Recommended circuit breaker Danfoss CTI-25M (small and
large unit) Code number:
0.37, 0.55 kW
0.75, 1.1 kW
1.5, 2.2, 3 kW
Recommended circuit breaker Danfoss CTI-45MB (small
(1)
unit) Code number:
0.55, 0.75 kW
1.1 kW
1.5 kW
2.2 kW
Power loss at maximum load [W]
(3)
Efficiency
Output current
Continuous (3x380–440 V) [A]
Intermittent (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (3x441–480 V) [A]
Continuous kVA (400 V AC) [kVA]
Continuous kVA (460 V AC) [kVA]
Maximum cable size: Mains, motor, brake. [mm2/(AWG)]
Maximum cable size: Mains, motor, brake. [mm2/(AWG)]
1) Type CTI-45MB circuit breakers are not available for 3 kW (4 hp) units.
2) Applies to the dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power
consumption are included. For power loss data according to EN 50598-2, refer to ecosmart.mydrive.danfoss.com.
3) Efficiency is measured at nominal current. For energy efficiency class, see
Danfoss A/S © 2025.04
PK37
0.37
0.5
1.2
1.9
1.0
1.6
gG-25
CTI-25M Code number: 047B3151
Code number: 047B3148
Code number: 047B3149
Code number: 047B3151
Code number: 047B3160
Code number: 047B3161
Code number: 047B3162
Code number: 047B3163
(2)
35
0.93
1.3
2.1
1.2
1.9
0.9
0.9
Solid cable: 6/(10)
Flexible cable: 4/(12)
7.4 Ambient
PK55
PK75
0.55
0.75
0.75
1.0
1.6
2.2
2.6
3.5
1.4
1.9
2.2
3.0
42
46
0.95
0.96
1.8
2.4
2.9
3.8
1.6
2.1
2.6
3.4
1.3
1.7
1.3
1.7
Conditions. For part load losses, refer to ecosmart.mydrive.danfoss.com.
Specifications
P1K1
P1K5
P2K2
1.1
1.5
2.2
1.5
2.0
3.0
2.7
3.7
5.0
4.3
5.9
8.0
2.7
3.1
4.3
4.3
5.0
6.9
58
62
88
0.96
0.97
0.97
3.0
4.1
5.2
4.8
6.6
8.3
3.0
3.4
4.8
4.8
5.4
7.7
2.1
2.8
3.9
2.4
2.7
3.8
AQ267036816112en-000301 / 130R0208 |
P3K0
3.0
4.0
6.5
10.4
5.7
9.1
116
0.97
7.2
11.5
6.3
10.1
5.0
5.0
63
Need help?
Do you have a question about the VLT FCD 302 and is the answer not in the manual?
Questions and answers