Operating Guide | VLT® Decentral Drive FCD 302
INTERNAL FAILURE HAZARD
An internal failure in the drive can result in serious injury when the drive is not properly closed.
Ensure that all safety covers are in place and securely fastened before applying power.
l
Overcurrent protection
Extra protective equipment, such as short-circuit protection or motor thermal protection between drive and motor, is required for
l
applications with multiple motors.
Input fusing is required to provide short-circuit and overcurrent protection. If not factory-supplied, the installer must provide fuses.
l
See maximum fuse ratings in
Wire type and ratings
All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements.
l
Power connection wire recommendation: Minimum 75 °C (167 °F) rated copper wire. See
l
sizes and types.
1.9 Disposal
Do not dispose of equipment containing electrical components together with domestic waste.
Collect it separately in accordance with local and currently valid legislation.
Danfoss A/S © 2025.04
4.9.2 Recommended Maximum Pre-fuse Size 25