Veeder-Root Red Jacket Quick-Set Installation, Operation And Service page 15

4” submersible petroleum pump
Hide thumbs Also See for Red Jacket Quick-Set:

Advertisement

4" Standard Pump Installation, Operation & Service Manual
Table 4. Electrical Service Information (Use For UMPs Containing A Faradyne Motor With End View B)
Required power supply rating for 60 Hz, 1 phase motors is 208 - 230 Vac. For 50 Hz, 1 phase motors, required rating is 220 - 240 Vac.
3 phase motors required rating is 380 - 415 Vac.
UMP Model No.
HP
AGUMP33R1,
1/3
UMP33R1
AGUMP75S1,
3/4
UMP75S1
AGUMP150S1,
1-1/2
UMP150S1
X3AGUMP150S1,
1/1/2
X3UMP150S1
AGUMP75S3-3,
3/4
UMP75S3-3
AGUMP150S3-3,
1-1/2
UMP150S3-3
X4AGUMP150S3,
1-1/2
X4UMP150S3
When using a Red Jacket IQ
(Version3.2) or newer, is required for proper operation of the system. The UMPs will have an 'FM' designation
printed on the UMP shell. Software upgrade kit part number is 410600-001.
Table 5 lists pump weights and lengths.
The weights and lengths listed below are approximate values and will vary due to manufac-
turing tolerances.
The optional trapper intake screen is available as a field installed accessory. Trapper options will change the length
of the UMP by 3.3 inches (83 mm). For installation instructions, see Red Jacket installation instructions #051-256-
1. For models with Floating Suction Adapter, add 2-3/8 inches (59 mm) and 4 pounds (1.8 kg).
Voltage
Fluctuation
Range
Hz
PH
Min.
Max.
Amps
60
1
200
250
60
1
200
250
60
1
200
250
60
1
200
250
50
1
200
250
50
1
200
250
50
1
200
250
TM
Control Unit with an UMP containing a Faradyne motor, IQ software 805-001C
Winding Resistance (Ohms)
Max.
Locked
Load
Rotor
Black-
Amps
Orange
4
10
8.9 - 10.8
6.5
19
4.7 - 5.7
10.5
33
2.8 - 3.4
10.5
33
2.8 - 3.4
5.8
18
5.2 - 6.3
10
31
2.8 - 3.4
10
31
2.8 - 3.4
10
Red-
Capacitor Kit
Orange
Black-Red
11.5 - 13.9
20.2 - 24.5
144-224-5 (17.5)
7 .1 - 8.6
11.7 - 14.1
144-224-5 (17.5)
6.8 - 8.2
9.4 - 11.3
144-225-5 (25)
6.8 - 8.2
9.4 - 11.3
144-225-5 (25)
10.3 - 12.5
15.4 - 18.6
144-224-5 (17.5)
13.4 - 16.3
16.1 - 19.5
144-225-5 (25)
13.4 - 16.3
16.1 - 19.5
144-225-5 (25)
Specifications