10.3. Step 3- Apply Power.
 Apply rated voltage to the
drive.
 Check that the drive displays
Apply Electrical
or
Power to the drive
10.4. Step 4- Motor nameplate data entry.
Action
Select Geared
 Set P4-01 to 0
(Induction) motor
control
Enter motor rated
 Enter value into P4-02
voltage (P4-02)
Enter Motor Rated
 Enter value into P4-03
Current (P4-03)
Enter Motor Rated
 Enter value into P4-04
Frequency (P4-04)
Enter Number of
 Enter value into P4-05
Motor Poles (P4-05)
Enter Motor Rated
 Enter value into P4-06
Speed (P4-06)
Enter Motor power
factor Cos Ø (P4-07)
 Enter value into P4-07
 Enter value into P8-01
Enter the Maximum
speed (P8-01)
10.5. Step 5- Motor Auto-tune.
A Motor Auto-tune must be carried out in order to measure the motor electrical characteristics, brakes will be applied by the drive (unless
controlled by other means) during this test.
Action
 If the motor contactor(s) are controlled by the elevator controller then they should be activated to close so that the motor is electrically
connected to the drive, otherwise the "Auto-tune" cannot be carried out.
 If the motor contactor(s) are controlled by the drive (connected to relay 1) the motor contactor will automatically be energised when the
"Auto-tune" is enabled.
 Check Safe Torque
off input
connections have
been made.
and press
 Enable Stationary
Motor Auto-tune
.
Enter Voltage value as shown on the motor nameplate (Volts).
Enter Current value as shown on the motor nameplate (Amps).
Enter Frequency value as shown on the motor nameplate (Hz).
Enter motor pole value as shown on the motor nameplate, if unknown set P4-05 to 0
where the drive will automatically calculate the value providing P4-04 (Motor rated
frequency) and P4-06 (Motor rated speed) have been entered correctly.
Enter motor rated speed value as shown on the motor nameplate (rpm).
The drive display will now show motor speed in estimated rpm. All speed related
parameters, such as Minimum and Maximum Speed, run Speeds etc. will also be
displayed in Rpm.
Obtained from Motor nameplate.
If Motor power factor is unknown leave as default value.
Note: When the motor is running, parameter P0-22 displays the measured power factor
value, and this can then be entered into P4-07.
This is the maximum allowable speed in rpm.
Set P4-08 to a 1
on the drive
keypad.
www.InvertekDrives.com
If or is not shown refer to the section 20 Troubleshooting.
Additional Information
Additional Information

Drive should now show
The STO input status can be viewed in parameter  (0 = Open 1 = Closed)
1.
The motor contactors will close (if controlled by the drive "Relay 1").
2.
The motor brakes will remain applied. (Relay 2 as default)

3.
The display will show
seconds to complete).
Note : If the drive trips refer to section 20 Troubleshooting.
4.
The motor contactors will open once the test has completed. (Relay 1
controlled by default)
Once the Auto-tune is completed P4-08 will return to 0 and the display will

show
(P4-24 thru to P4-28 will be populated).
Note: Motor Auto-tune will need to be repeated if the motor, motor cables,
motor parameters or drive control mode is changed in P4-01.
if not see section 20 Troubleshooting.