Download Print this page

Field Controls SWG-3 Product Manual page 37

Hide thumbs Also See for SWG-3:

Advertisement

DRAFT INDUCERS
GAS-FIRING WITH
DRAFT HOOD
Pipe
Draft
Input
Dia.
Inducer
Pressure (IN
(BTU/HR)
(IN)
(Model)
69,000
3
105,000
4
DI-1
1 1 1,000
5
120,000
6
279,000
5
308,000
6
DI-2
330,000
7
353,000
8
522,000
8
674,000
9
DI-3
694,000
10
835,000
12
900,000
10
1,250,000
12
DI-4
1,400,000
14
1,800,000
16
2,000,000
14
2,200,000
16
DI-5
2,400,000
18
2,800,000
20
CONTROL KITS (CK) CONTROL THE OPERATION OF FIELD DRAFT INDUCERS.
SEE THE CHART BELOW TO SELECT THE PROPER KIT FOR YOUR APPLICATION.
MODEL
SINGLE NON CONDENSING OIL FIRED SYSTEM WITH 120 VAC SAFETY
CONTROL CIRCUIT. ALL REQUIRE A SINGLE ACTING DRAFT CONTROL
CK-63
APPROVED FOR OIL. MAY REQUIRE OPTIONAL DELAY VALVE FOR
SIMULTANEOUS POST PURGE POWER VENTER BURNER OPERATION.
SINGLE DRAFT-HOOD EQUIPPED GAS FIRED 30 TO 750 MILLIVOLT WATER
CK-20FV
HEATER, POOL HEATER OR SPA HEATER WITH A MANUAL OR INTERNALLY
MOUNTED THERMOSTAT.
SINGLE DRAFT-HOOD EQUIPPED GAS FIRED FURNACE, BOILER, UNIT
CK-41F
HEATER OR WATER HEATER OPERATING WITH A 24 VAC GAS VALVE
CK-41P**
WITHOUT FACTORY MOUNTED THERMAL SAFETY SWITCHES.
CK-43
SINGLE DRAFT INDUCED GAS FIRED NON CONDENSING FURNACE,
BOILER OR UNIT HEATER WITH A 24 VAC GAS CONTROL CIRCUIT.
CK-43F
INCLUDES 4 INCH MG-1 DRAFT CONTROL AND POST PURGE.
SINGLE DRAFT INDUCED NON CONDENSING GAS FIRED FURNACE,
BOILER OR UNIT HEATER WITH A 24 VAC GAS CONTROL CIRCUIT AND A
CK-91FV
DRAFT HOOD EQUIPPED GAS FIRED 30 TO 750 MILLIVOLT WATER HEATER.
INCLUDES POST PURGE AND 4 INCH MG-1 DRAFT CONTROL FOR THE
DRAFT INDUCED APPLIANCE.
DRAFT-HOOD EQUIPPED GAS FIRED - FURNACE, BOILER, UNIT HEATER
CK-92FV
WITH 24 VAC GAS CONTROL CIRCUIT AND A DRAFT HOOD EQUIPPED 30
CK-92FVP**
TO 750 MILLIVOLT GAS FIRED WATER HEATER.
** Plugs into 24v electric damper
F = Fixed Post Purge FV= right hand threaded TCA Safety Switch
36
SIZING CHART
GAS-FIRING WITH
BAROMETRIC DRAFT CONTROL
Static
Pipe
Flow
Input
Dia.
(CFM)
(BTU/HR)
W.C.)
(IN)
.04
47
69,000
3
.04
72
105,000
4
.06
75
1 18,000
5
.05
82
123,000
6
.06
190
300,000
5
.07
210
340,000
6
.1 1
225
364,000
7
.07
240
390,000
8
.18
355
683,000
8
.15
458
880,000
9
.12
472
908,000
10
.08
568
1,092,000
12
.18
612
1,177,000
10
.20
850
1,635,000
12
.19
952
1,831,000
14
.15
1,224
2,300,000
16
.14
1,224
2,350,000
14
.18
1,500
2,885,000
16
.10
1,632
3,140,000
18
.09
1,900
3,654,000
20
APPLICATIONS
Draft
Static
Flow
Max. Input
Inducer
Pressure (IN
(CFM)
per GPH
(Model)
W.C.)
.05
36
.5
.05
55
.7
DI-1
.06
65
.9
.05
68
.95
.07
156
2
.08
176
2.5
DI-2
.09
189
2.75
.06
200
3
.15
355
5
.13
458
6
DI-3
.10
472
6.5
.06
568
7.5
.15
612
8.5
.17
850
1 1
DI-4
.16
952
13
.13
1,224
17
.12
1,224
17
.15
1,500
21
DI-5
.09
1,632
22
.08
1,900
26
3
3
3
3
3
3
Customer Service:
OIL OR COAL-FIRING WITH
BAROMETRIC DRAFT CONTROL
Draft
Static
Pipe Dia.
Flow
Inducer
Pressure
(IN)
(CFM)
(Model)
(IN W.C.)
3
.05
36
4
.05
48
DI-1
5
.05
67
6
.04
68
5
.06
156
6
.07
175
DI-2
7
.08
200
8
.05
215
8
.13
355
9
.1 1
458
DI-3
10
.09
472
12
.06
568
10
.13
612
12
.14
850
DI-4
14
.13
952
16
.10
1,224
14
.10
1,224
16
.13
1,500
DI-5
18
.07
1,632
20
.06
1,900
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
252.522.3031

Advertisement

loading
Need help?

Need help?

Do you have a question about the SWG-3 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Swg-4hdSwg-4hdsSwg-5Swg-5sSwg-6Swg-6s ... Show all