FORM 160.54-M1
TABLE 26 - FLASH MEMORY CARD VERSION C.MLM.01.08.XXX
CHILLER STYLE/
PROXIMITY
COMPRESSOR
"Style CDE/GHJ Compr"
"Style E/P Compr"
"Style F/GH Compr"
"Style F/J Compr"
"Style F/P, Compr"
* Not applicable to Style C (and earlier) chillers
TABLE 27 - FLASH MEMORY CARD VERSION C.MLM.01.08.105A AND C.MLM.01.08.206A (AND LATER)
CHILLER STYLE/
PROXIMITY
COMPRESSOR
"Style CDE/GHJ Compr"
"Style E/P Compr"
"Style F/G, H5-8 Compr"
"Style F/J, H3 Compr"
"Style F/P, Compr"
* Not applicable to Style C (and earlier) chillers
TABLE 28 - SOFTWARE VERSION C.MLM.01.10B.XXX (AND LATER) OR C.OPT.01.10B.XXX (AND LATER)
PROXIMITY
CHILLER STYLE/
COMPRESSOR
"Style CDE/GHJ Compr"
"Style E/P Compr"
"Style F/G, H5-8 Compr"
"Style F/J, H3 Compr"
"Style F/P, Q LH9
Compr"
JOHNSON CONTROLS
SECTION 32 - SYSTEM CALIBRATION, SERVICE SETPOINTS AND RESET PROCEDURES
OIL
CONTROL
HEATER
SENSE
OUTPUT*
Probe
TB1-34
Limit Switch
TB1-64
Limit Switch
TB1-64
Probe
TB1-64
Limit Switch
TB1-64
OIL
CONTROL
HEATER
SENSE
OUTPUT*
Probe
TB1-34
Limit Switch
TB1-64
Limit Switch
TB1-64
Probe
TB1-64
Limit Switch
TB1-64
OIL
CONTROL
HEATER
SENSE
OUTPUT*
Probe
TB1-34
Limit Switch
TB1-64
Limit Switch
TB1-64
Probe
TB1-64
Limit Switch
TB1-64
LEVEL
FLOW
PERIOD
SWITCH
DEFAULT
Digital
3.5 sec
(Paddle Type)
Digital
10.0 sec
(Paddle Type)
Programmable
3.5 sec
(Analog or Digital)
Programmable
3.5 sec
(Analog or Digital)
Programmable
10.0 sec
(Analog or Digital)
LEVEL
FLOW
PERIOD
SWITCH
DEFAULT
Digital
3.5 sec
(Paddle Type)
Digital
10.0 sec
(Paddle Type)
Programmable
3.5 sec
(Analog or Digital)
Programmable
3.5 sec
(Analog or Digital)
Programmable
10.0 sec
(Analog or Digital)
LEVEL
FLOW
PERIOD
SWITCH
DEFAULT
Digital
3.5 sec
(Paddle Type)
Digital
10.0 sec
(Paddle Type)
Programmable
3.5 sec
(Analog or Digital)
Programmable
3.5 sec
(Analog or Digital)
Programmable
10.0 sec
(Analog or Digital)
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
35 PSID
25 PSID
35 PSID
35 PSID
25 PSID
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
35 PSID
25 PSID
35 PSID
35 PSID
25 PSID
OIL-VARIABLE SPEED PUMP
PRESSURE SETPOINT NOT
ACHIEVED THRESHOLD*
35 PSID
25 PSID
35 PSID
35 PSID
35 PSID
265