Centrifugal liquid chillers, r-134a or r-513a with optiview control center for electromechanical starter, solid state starter, and variable speed drive (56 pages)
Summary of Contents for Johnson Controls YORK YPC Series
Page 1
TWO-STAGE ABSORPTION CHILLERS INSTALLATION Supersedes: 155.17-N1 (900) Form 155.17-N1 (413) MODEL YPC DIRECT-FIRED YPC-FA-12SC THROUGH YPC-FZ-19S AND STEAM-FIRED YPC-ST-14SC THROUGH YPC-ST-19S Steam-Fired LD17247 Direct-Fired LD17267 Issue Date: April 1, 2013...
Page 2
All wiring must be in accor- dance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 155.17-N1 ISSUE DATE: 4/1/2013 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for contin- these documents, the technician should verify whether uous product improvement, the information contained the equipment has been modified and if current litera- in this document is subject to change without notice.
Page 4
FB = Direct-Fired (No. 2 oil only) FA = Direct-Fired (Other fuels) FR = Direct-Fired (Natural gas with low NO FGR only) FC = Direct-Fired (Natural gas with low NO FGR / No. 2 oil) ST = Steam Heat Model = York ParaFlow Chiller JOHNSON CONTROLS...
Page 6
SECTION 20 – DRAFT CONTROL .........................63 SECTION 21 – BAROMETRIC DAMPERS ......................65 SECTION 22 – SEQUENTIAL DRAFT CONTROL (Motorized Draft Control) ............. 67 Backdraft Damper ............................67 Not recommended to mount vertically reasons: ..................67 SECTION 23 – HIGH STACK TEMPERATURE PROBE ..................69 JOHNSON CONTROLS...
Page 7
Energy Management Systems Wir ing ......................83 SECTION 30 – INSULATION ..........................85 Insulation Tips ..............................85 Other Insulation Guidelines ..........................86 Additional Comments ............................. 86 APPENDIX A - TABLES ............................87 APPENDIX B - RIGGING ILLUSTRATIONS ......................95 APPENDIX C - INSULATION ILLUSTRATIONS ....................99 JOHNSON CONTROLS...
Page 8
FIGURE 52 - Insulation Diagram, Model YPC-DF-15SL-19S ................106 FIGURE 53 - Insulation Diagram, Model YPC-ST-14S, 16SL-19S ..............108 FIGURE 54 - Insulation Diagram, Model YPC-ST-14S, 16SL-19S ..............110 FIGURE 55 - Insulation Diagram, Auxillary Views ....................112 JOHNSON CONTROLS...
Page 9
TABLE 15 - S-Unit Rigging ............................. 95 TABLE 16 - Absorption Insulation Legend ......................99 TABLE 17 - York Paraflow™ Absorption Chiller Insulation Area (Sq. Feet) ............99 TABLE 18 - York Paraflow™ Absorption Chiller Insulation Area (Sq. Meters) ............99 JOHNSON CONTROLS...
Page 10
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
2. Accurately estimate the cost of his work. Johnson Controls rep re sen ta tives are available to an- 3. Assure proper, timely and trouble-free unit in stal- swer any and all questions and to coordinate de liv ery la tion.
Page 12
The end opposite the tube pull end should be allowed 60 inches of ser- vice clear ance. Refer to Appendix A, Unit Weights and Dimensions for specific Unit Clearance Data. JOHNSON CONTROLS...
When sat is fied that the unit installation is com plete, call for the ser- vic es of a Johnson Controls rep re sen ta tive by filling out the form and sub mit ting to the local Johnson Con- trols service of fice.
Page 14
........2. No visible signs of damage ........6. All thermometer wells, flow switches and gauge 3. With a local YORK / Johnson Controls Service connections installed in chilled and condenser Representative present, open all containers and water lines ............
Page 15
7. High stack temperature probe installed properly 1. Lithium Bromide, refrigerant and alcohol avail- and wired ............able at jobsite for YORK / Johnson Controls 8. Have properly sized vent lines been installed Service to charge the unit ........on all fans train components with require 2.
Page 16
Year We understand that the services of the Johnson Controls Authorized Representative will be furnished in accordance with the contract for a period of time of not more than _______ consecutive normal working hours, and we agree that a charge of _________ per diem plus travel expenses will be made to Johnson Controls if services are required for longer than ________ consecutive normal hours or if repeated calls are required, through no fault of Johnson Controls.
If the unit is to be installed sions, and weights. in a sub lev el basement or where it can only be rigged slanted, contact Johnson Controls for spe- cial instructions prior to rigging. This should be done prior to ordering, to check feasibility.
Page 18
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
IMPORTANT STEPS TO FOLLOW DURING REASSEMBLY All cutting and welding of units under warranty must be 100% Johnson Controls supervised. Under no cir- Welds that cannot be pressure tested must be dye pen- cumstances should non-Johnson Controls personnel etrant tested prior to closing. Solution pipes within...
Page 20
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
00296VIP WATER LEVEL SEMI-TRANSPARENT VINYL HOSE Level Marker Jacking Point 1000 1000 MAXIMUM ALLOWABLE OUT-OF-LEVEL TOLERANCE BETWEEN ANY TWO CORNERS 00294VIP LD05299 FIGURE 4 - LEVELING AND ANCHORING THE UNIT FIGURE 5 - JACKING POINT JOHNSON CONTROLS...
COOLING TOWER 3-WAY BYPASS VALVE TOWER PUMP CONDENSER EVAPORATOR ABSORBER HOT WATER HEATER ld05302 FIGURE 8 - TYPICAL WATER PIPING SCHEMATIC, ALL UNITS - MODELS 12SC THROUGH 22G JOHNSON CONTROLS...
An evaporator water flow switch is sup plied by tubes, coils, and controls. The strainer should be a #10 Johnson Controls as a ship loose item. This water flow mesh and be installed in the entering water line, direct- switch must be in stalled in either the evaporator sup- ly upstream of the chiller.
2. row mark on side of casting must point in same 4-5/8" direction as liquid flow.) 5-5/8" 3. The Flow Switch can be installed in either the in- 8 and Larger Full Paddle let flow or outlet flow connections. FIGURE 9 - INSTALLATION OF FLOW SWITCH JOHNSON CONTROLS...
ParaFlowTM Chiller/Heater, all unit system water piping must be leak checked and flushed. All water strainers must be cleaned after flushing and trapped air vented. ld05846 FIGURE 10 - PIPING FOR TOWER WATER - THREE-WAY MIXING VALVE JOHNSON CONTROLS...
The use of cor- rosion inhibitors must be effective at low concentra- Your local Johnson Controls Service Representative tions, must not cause deposits on the metal surfaces, will be more than happy to supply any or all of these and must remain effective under a broad range of pH, services.
Page 28
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
(BY OTHERS) 00295vip RUPTURE DISK AS SUPPLIED FROM FACTORY RUPTURE DISK VENT PIPING CPVC OR FIBERGLASS PIPE (BY OTHERS) PIPING SUPPORT (BY OTHERS) 10 - 12 INCHES FLOOR DRAIN ld05305 FIGURE 11 - TYPICAL RUPTURE DISK VENT PIPING JOHNSON CONTROLS...
Page 30
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
To control the steam flow through the tect the ab sorp tion unit from crystallization in the case chill er, Johnson Controls factory supplies a flow set- of a cycling/safety shut down or a power fail ure. The ting needle valve on the steam condensate return line.
The steam trap (mounted below the steam separator) will pre vent any This valve is sup plied by the Johnson Controls fac to- steam from blow ing through the separator and into the ry and can be found among the unit’s shipped loose condensate re turn sys tem.
∆ P Piping = Pressure drop due to condensate piping, start-up to fine-tune the condensate flow setting valve. elbows, bends, etc... ∆ P Valve = Pressure drop due to condensate system backpressure valve. JOHNSON CONTROLS...
Page 36
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Your local Johnson Controls Service Representative yses. A third party consulting company can help over- will be more than happy to supply any or all of these see the treatment programs in order to properly protect services.
Page 38
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Johnson Controls control panel. The gas train and fuel oil pump (if oil factory. The units are shipped with the burner pre- burner) are shipped separately and will require field wired to the appropriate con trol pan el.
Oil Return Piping Main Gas Shut-O Valve Oil Compound Gauge Union Manual Leak Test Shut-O Valve Burner Unit Main Gas Shut-O Cock Gas Pressure Gauge Burner Control Panel LD05307 FIGURE 14 - TYPICAL BURNER ASSEMBLY FOR DIRECT-FIRED, S-MODEL UNITS JOHNSON CONTROLS...
Switch Modulating Gas Valve Oil Check Valves Manual Gas Cock Gas Valve Jack Shaft Oil Valve Varicam Fuel Me- Blast Tube Linkage Set Linkage Set Linkage Set tering System 00270VIP FIGURE 16 - TYPICAL BURNER COMPONENTS (RIGHT-SIDE VIEW) JOHNSON CONTROLS...
Blower Motor Switch sure Gauge Oil Modulating Valve Pilot Gas Motorized Regulator Gas Valve Pilot Gas Valves Firing Rate Pilot Ignition Modulating Oil Solenoid Transformer Flame Sight Motor Valves Glass 00269VIP FIGURE 19 - TYPICAL BURNER COMPONENTS (BACK END) JOHNSON CONTROLS...
Pressure Tap Drip Leg Field Piped Test Cock Test Cock CAUTION: All eld mount components must be mounted in the proper location and in the proper direction of gas ow. LD05310 FIGURE 21 - TYPICAL SCHEMATIC GAS PIPING JOHNSON CONTROLS...
Page 46
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
TO BE SUPPLIED BY CUSTOMER CAUTION: ALL FIELD COMPONENTS MUST BE MOUNTED IN THE PROPER LOCATION AND DIRECTION OF OIL FLOW. CAUTION: OIL SUPPLY MUST NOT EXCEED 3 PSI PER NFPA CODE LD05311 FIGURE 22 - TYPICAL SCHEMATIC OIL PIPING JOHNSON CONTROLS...
CAUTION: ALL FIELD PIPING MUST BE 3/8" NPTF CHECK VALVE MOUNTED IN THE PROPER LOCATION RETURN PORT AND IN PROPER DIRECTION OF GAS FLOW. RETURN TO TANK LD05313 FIGURE 24 - OIL PIPING SCHEMATIC FOR WEBSTER “C” STYLE PUMP JOHNSON CONTROLS...
CHECK CHECK VALVE VALVE PUMP SET FROM VALVE TANK COMPOUND GAUGE FROM CIRCULATING OIL RESERVOIR (MAY BE PLACED HORIZONTALLY - SEE DETAIL A) ADDITIONAL BURNERS AS REQUIRED LD05314 FIGURE 25 - TYPICAL OIL PIPING SCHEMATIC FOR MULTIPLE BURNERS JOHNSON CONTROLS...
Page 50
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
SUCTION CAPACITY IN G.P.H TOTAL FEET OF 3/8" O.D. TOTAL FEET OF 1/2" O.D. TOTAL FEET OF 5/8" O.D. TOTAL FEET OF 3/4" O.D. COPPPER TUBING COPPPER TUBING COPPPER TUBING COPPPER TUBING LD05315 FIGURE 26 - OIL LINE SIZING GRAPHS JOHNSON CONTROLS...
Page 52
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
#2 fuel oil, the entire system should be thorough- oil leak tests should be performed. Make certain that ly cleaned and flushed before filling the tank with the the tank atmospheric vent line is unobstructed. new #2 fuel oil for the first time. JOHNSON CONTROLS...
Page 54
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Wood lou vers and grills will have 20 - 25% free area openings: one com menc ing within 12 inches (30cm) and met al lou vers and grills will have 60 - 75% free area. of the ceiling, and one com menc ing 12 inches (30cm) from the floor. JOHNSON CONTROLS...
“Main Flame On” con tacts can close. Oth er wise, a OUTDOORS 12" MECHANICAL ROOM INTERSTITIAL LOUVERS/GRILLS LOUVERS/GRILLS SPACE PARAFLOW 12" CHILLER/HEATER MECHANICAL ROOM FLOOR LD05316 FIGURE 27 - COMBUSTION AND VENTILATION AIR IN MECHANICAL ROOMS JOHNSON CONTROLS...
If in doubt regard- engineer the air intake re quire ments for his burn er at ing the air flow capabilities of a chosen the proper operating conditions. duct size, the next largest size duct is recommended. JOHNSON CONTROLS...
Page 58
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
+/- 50°F (23.6°C). ambient air. The magnitude of this temperature differ- ence is directly proportional to the draft created. Tem- perature differences cause drafts be cause gases such as air occupy different volumes at dif fer ent temperatures. JOHNSON CONTROLS...
Chimney design and draft control are topics best han- Theoretical draft is a function of mean or net chim- dled by experienced engineers. Johnson Controls ney gas tem per a ture (always a tem per a ture lower than strongly recommends that the installer engage the ser-...
Johnson Controls will not be re spon si ble for costs as so ci at ed with ret ro fit ting damp ers to im prop er- With the gauge pressure thus stabilized just upstream ly de signed chim neys.
VALVE FLANGE A – PARAFLOW EXHAUST FLANGE FLANGE B – ROUND END FLANGE OF REMOVABLE TRANSITION PIECE (DIMENSIONS PER SUBMITTAL INFORMATION, (ID DETERMINED BY CHIMNEY SYSTEM DESIGNER) OR SEE APPROPRIATE YORK FORM) LD05320 FIGURE 31 - BAROMETRIC CONTROL JOHNSON CONTROLS...
Figure 32 on page 67 and Figure 33 on page 68 BACKDRAFT DAMPER depict a sequential draft control system. This type of The Johnson Controls supplied manual backdraft system incorporates an actuator motor mounted on top damper can be modified (in the factory if ordered, or of the damper assembly.
FLANGE A – PARAFLOW EXHAUST FLANGE FLANGE B – ROUND END FLANGE OF REMOVABLE TRANSITION PIECE (DIMENSIONS PER SUBMITTAL INFORMATION, (ID DETERMINED BY CHIMNEY SYSTEM DESIGNER) OR SEE APPROPRIATE YORK FORM) LD05321 FIGURE 33 - SEqUENTIAL DRAFT CONTROL JOHNSON CONTROLS...
The probe will require a 1/8" NPTI man u al backdraft damp er, if pos si ble. If this is not pos- coupling, which must be sup plied by the field in stall er. JOHNSON CONTROLS...
Page 70
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
For all European direct-fired unit shipments re quir- MODEL IDENTIFICATION ing 50 Hz CE code wiring, Johnson Controls sup plies The following is an example of a Weishaupt burner a Weishaupt burn er in lieu of a Power Flame burner.
This test is necessary cord ing ly due to local codes, firing rates of the burner, and is re quired for the Weishaupt burner commission- or gas sup ply pres sure. ing report, which must be submitted to Weishaupt for warranty. JOHNSON CONTROLS...
TANK BURNER MANUAL SHUT-OFF FILTER VALVES (MECHANICALLY LINKED) LD05324 FIGURE 36 - OIL PIPING SCHEMATIC - OIL TANK LOCATED HIGHER THAN BURNER JOHNSON CONTROLS...
A SCALE HORIZONTAL 82.5 VERTICAL B SCALE 86.5 84.5 AXIAL C SCALE 87.5 UNITS: MICRONS UNITS: dB AT 1 METER DISTANCE FROM THE CHILLER LD05328 FIGURE 40 - TYPICAL NOISE AND VIBRATION LEVELS - STEAM-FIRED UNITS, ALL MODELS JOHNSON CONTROLS...
Page 80
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Johnson the ap pro pri ate Johnson Controls forms as listed at the Controls service (this should be determined at the time front of this doc u ment under the Introduction Section.
1 and 2 on Digital Input Board TB2. PURGE PUMP MOTOR Hot Water Flow Switch (where applicable), contacts 1 and 82 on Relay Board TB4. LD05329 LD05330 FIGURE 42 - WIRING THE PURGE PUMP FIGURE 43 - FLOW SWITCH CONNECTIONS JOHNSON CONTROLS...
Page 84
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Johnson Controls performance ratings are based on a prop er ly in su lat ed chiller. Proper insulation limits the INSULATION TIPS heat loss from the chiller to its surroundings. Insula- tion also protects personnel from the hot surfaces, such Before insulating an absorption chiller, see the “Other...
Insulation should be These areas must be accessible for service and occa- sched uled last. Johnson Controls will not be respon- sionally by operating personnel. NEVER cover sight sible for costs incurred to remove insulation to leak glass areas.
NOTES: * BZT (Benzotriazole) is supplied with the chiller from the factory as part of the chiller’s ship loose parts. It is for a one time only installation by a qualified Johnson Controls Service Technician in the first stage generator of steam fired units at chiller start-up.
19.9 / 28 22G* 1500 CR5-G(O)-30 10,418 3000 19.9 / 28 NOTES: Units equipped with two burners This information is of a general nature only. Please refer to “Burner As Built Data” (supplied with burner) for specific job details. JOHNSON CONTROLS...
*To be used for specific gravities or pressure drops TABLE 9 - EqUIVALENT LENGTH OF FITTINGS (FT.)* PIPE SIZE (IPS) 1.25 STD. TEE THROUGH SIDE 12.0 14.0 17.0 22.0 STD. E11 12.0 45° E11 PLUG COCK 12.0 16.0 *Based on schedule 40 iron pipe JOHNSON CONTROLS...
5. Connection lugs in power panel will accept incoming wire range of #14 AWG through #1/0 AWG for 380 volt and 460 volt chillers. For 200, 208 and 230 volt chillers, lugs will accept #4 to 350 MCM wire. JOHNSON CONTROLS...
5. Connection lugs in power panel will accept incoming wire range of #14 AWG through #1/0 AWG for 380 volt and 460 volt chillers. For 200, 208 and 230 volt chillers, lugs will accept #4 to 350 MCM wire. JOHNSON CONTROLS...
Page 93
FORM 155.17-N1 APPENDIX A - TABLES ISSUE DATE: 4/1/2013 JOHNSON CONTROLS...
Page 94
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
NOTE: For lifting units, sling vertically. Use extreme care so as not to sling against, or on any projecting brackets, pipes, fittings, etc. Use four slings and spreader bar as shown, one sling on each end of the first-stage generator and one on each end of the main shell. LD05334 FIGURE 46 - RIGGING FOR 19G THROUGH 19GL DIRECT-FIRED UNITS JOHNSON CONTROLS...
NOTE: For lifting units, sling vertically. Use extreme care as not to sling against, or on any projecting brackets, pipes, fittings, etc. Use spreader bar as shown and two slings. Sling around belly bands on the main shell - when lifting, make certain unit is level. LD05336 FIGURE 48 - RIGGING FOR 19G THROUGH 22GL STEAM-FIRED UNITS JOHNSON CONTROLS...
Page 98
FORM 155.17-N1 ISSUE DATE: 4/1/2013 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
6. Do not use weld pins to attach insulation. To mount insulation materials, use bonding agents, wires or bands. These methods do not penetrate the chiller system and jeopardize the integrity of the vacuum pressure in the chiller. WELD PINS ARE NOT ACCEPTABLE. JOHNSON CONTROLS...