Table 11 - Pressure Transducer Applications - Johnson Controls YORK OPTIVIEW YK Series Service Instructions Manual

Centrifugal liquid chillers with optiview control center
Table of Contents

Advertisement

FORM 160.54-M1
FIGURE 70 - PRESSURE TRANSDUCERS (CONT'D)

TABLE 11 - PRESSURE TRANSDUCER APPLICATIONS

TRANSDUCER
PART NUMBER*
025-28678-001
025-28678-102
025-28678-113
025-28678-103
025-28678-114
025-28678-004
025-28678-006
025-28678-112
025-28678-104
025-28678-115
025-39464-000
025-40088-000
* Note: Transducers 025-28678-001, -004, -102 and -103, 104 have NPTF threads.
Transducers 025-28678-006, -112, -113, -114 and 025-39464-000 and 025-40088-000 have straight threads with O-rings.
JOHNSON CONTROLS
+ 0.10
0.75
6
62.5
0.500
2.5
PRESSURE (PSIG)
NOMINAL OUTPUT VOLTAGE
EVAPORATOR TRANSDUCER
YORK PART NO. 025-28678-115
V = P + 15.63
P = (31.25 x V) - 15.63
31.25
V = VOLTS DC
P = PRESSURE (PSIG)
FUNCTION
Condenser, High Oil
Evaporator
Evaporator
Low Oil
Condenser, Hi and Lo Oil
Evaporator
Evaporator
Evaporator (Heat Pump Duty)
Stall Detection
SECTION 19 - PRESSURE TRANSDUCERS
125
PRESSURE (PSIS)
NOMIAL OUTPUT
4.500
VOLTAGE
LD15644
R22
APPLICATION
WATER
X
X
X
R-134a
X
X
X
X
X
19
BRINE
X
X
X
X
X
X
X
X
153

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YORK OPTIVIEW YK Series and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents