Table 20 - Leaving And Return Heating Condenser Water Temperature Sensor - Johnson Controls YORK OPTIVIEW YK Series Service Instructions Manual

Centrifugal liquid chillers with optiview control center
Table of Contents

Advertisement

FORM 160.54-M1

TABLE 20 - LEAVING AND RETURN HEATING CONDENSER WATER TEMPERATURE SENSOR

TEMP (°F) TEMP (°C)
32.63
0.35
37.47
3.03
42.23
5.68
46.96
9.97
51.68
10.93
56.44
13.57
61.28
16.26
66.23
19.01
71.36
21.86
76.70
24.61
82.32
27.955
88.31
31.28
94.74
34.85
101.8
38.77
109.6
43.11
118.5
48.05
128.9
53.83
141.7
60.94
158.2
70.11
JOHNSON CONTROLS
VIN
1.713
1.870
2.026
2.182
2.338
2.495
2.651
2.807
2.963
3.120
3.276
3.432
3.588
3.745
3.901
4.057
4.213
4.370
4.526
SECTION 20 - TEMPERATURE THERMISTORS
20
175