Centrifugal liquid chillers, r-134a or r-513a with optiview control center for electromechanical starter, solid state starter, and variable speed drive (56 pages)
Summary of Contents for Johnson Controls YORK OPTIVIEW YK Series
Page 1
CENTRIFUGAL LIQUID CHILLERS WITH OPTIVIEW™ CONTROL CENTER SERVICE INSTRUCTIONS Supersedes: 160.54-M1 Form 160.54-M1 OPTIVIEW™ CONTROL CENTER MODEL YK (THROUGH STYLE G) 00614VIP...
Page 2
All wiring must be in accordance with Johnson Controls’ published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals.
Page 3
FORM 160.54-M1 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for con- these documents, the technician should verify whether tinuous product improvement, the information con- the equipment has been modified and if current litera- tained in this document is subject to change without ture is available from the owner of the equipment prior notice.
-111 Mod B Solid State Starter or Variable Speed Drive w/Modbus Communications and VGD, no J7 compressor – CE -112 Mod B Solid State Starter or Variable Speed Drive w/Modbus Communications and VGD, J7 compressor – NEMA 1 JOHNSON CONTROLS...
Page 6
Stall Detector Board ............................ 201 SECTION 26 - LARGE TONNAGE CHILLER (LTC) I/O BOARD ...............205 Digital Inputs ..............................205 Digital Outputs .............................. 207 Analog Inputs ............................... 208 Analog Outputs ............................. 209 Auto Detection ............................. 210 Diagnostic Screen ............................210 JOHNSON CONTROLS...
Page 7
High Condenser Pressure Warning Threshold ..................... 257 Brine Low Evaporator Pressure Cutout ......................258 Leaving Chilled Liquid Temperature Control Sensitivity ................258 Drop Leg Refrigerant Temperature ....................... 258 Smart Freeze Protection ..........................259 Evaporator Refrigerant Temperature ......................259 Hot Gas Bypass Control ..........................259 JOHNSON CONTROLS...
Page 8
SI0212 - Software Enhancements (Ver 21) Effective June 2009 ..............333 SI0224 - Software Enhancements (Ver 22) Effective April 2010 ..............338 SI0252 - Software Enhancements (Ver 23) Effective May 2011 ..............339 SI0265 - Software Enhancements (Ver 24) Effective May 2012 ..............342 JOHNSON CONTROLS...
Page 11
FIGURE 105 - Serial Inputs / Outputs Test Screen ....................289 FIGURE 106 - Microboard - COM 5 Serial Data Port ....................290 FIGURE 107 - Digital inputs / Outputs Test Screen ....................291 FIGURE 108 - Analog Inputs Test Screen ......................294 JOHNSON CONTROLS...
Page 12
TABLE 27 - Flash Memory Card Version C.MLM.01.08.105A and C.MLM.01.08.206A (and later) ...... 265 TABLE 28 - Software Version C.MLM.01.10B.XXX (and later) or C.OPT.01.10B.XXX (and later) ...... 265 TABLE 29 - Software Version C.OPT.01.16.XXX (and later) ................266 TABLE 30 - Loop Back Connections ........................341 TABLE 31 - SI Metric Conversion .........................345 JOHNSON CONTROLS...
OptiView™ Control Cen- lem through the system. Use the Diagnostic Routines ter keypad, how to enter setpoints and explains all the where appropriate. messages displayed on the OptiView™ Control Cen- JOHNSON CONTROLS...
Page 14
FORM 160.54-M1 SECTION 1 - INTRODUCTION THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
Typical output voltage range of both is ure 8 on Page 27 and Figure 9 on Page 28 0.5 to 4.5VDC. These are Analog Inputs to the OptiV- are Operation Sequence timing diagrams of the iew™ Control Center. different starter applications. JOHNSON CONTROLS...
Page 16
Since the newer versions microboard are backward Refer to SECTION 25 - VARIABLE GEOMETRY DIF- compatible to earlier vintage OptiView™ Control Cen- FUSER. ters, earlier chillers could be equipped with a later ver- sion microboard due to service replacement. JOHNSON CONTROLS...
Page 17
Figure 15 on Page 45. and condenser. These are electronic thermal-type sen- sors. Flash memory card version C.MLM.01.07.xxx and C.MLM.01.07A.xxx automatically selects the flow sensor input, either digital or analog per the chiller style/compressor setpoint selection. JOHNSON CONTROLS...
Page 18
B LCSSS (after mid 2008) use Modbus protocol (re- quires software version C.OPT.01.18.307 or later). Stall may occur at low load conditions with high head. A mechanical ring, located in the compressor diffuser passage is operated to open or close the diffuser gap. JOHNSON CONTROLS...
Page 19
If the chiller is provided with a compressor motor VSD conditions. Software version C.OPT.01.22.307 (and or the optional hot gas bypass, the PRV potentiometer later) is required for this feature. for those features is used. Otherwise, a PRV potenti- ometer is provided interfaced to the microboard. JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 2 - SYSTEM ARCHITECTURE FIGURE 4 - OPTIVIEW™ CONTROL CENTER - MEDIUM VOLTAGE SOLID STATE STARTER APPLICATIONS JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 2 - SYSTEM ARCHITECTURE FIGURE 5 - OPTIVIEW™ CONTROL CENTER - COMPRESSOR MOTOR VARIABLE SPEED DRIVE (YORK SERIAL COMMUNICATIONS PROTOCOL) JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 2 - SYSTEM ARCHITECTURE FIGURE 6 - OPTIVIEW™ CONTROL CENTER - COMPRESSOR MOTOR VARIABLE SPEED DRIVE (MODBUS SERIAL COMMUNICATIONS PROTOCOL) JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 2 - SYSTEM ARCHITECTURE FIGURE 7 - OPTIVIEW™ CONTROL CENTER - COMPRESSOR MOTOR MEDIUM VOLTAGE VARIABLE SPEED DRIVE JOHNSON CONTROLS...
(1.83) (10) START START CLOSED RESTART RESTART (IF FIVE SUCCESSIVE CLOSE (ONLY AFTER FIFTH RESTARTS HAVE NOT TIME IN SECONDS (MINUTES) SUCCESSIVE RESTART) OCCURED) LD06504 FIGURE 9 - OPERATION SEQUENCE TIMING DIAGRAM (COMPRESSOR MOTOR VARIABLE SPEED DRIVE APPLICATIONS) JOHNSON CONTROLS...
Refer to YORK Renewal and revision level. The version is printed on a label ad- Parts - OptiView™ Control Center (Form hered to the memory card’s surface. The version code 160.54-RP1) and Service Replacement is as follows: paragraph in this manual. JOHNSON CONTROLS...
Page 30
The watchdog circuit also assures that all the program instructions are being performed and that the Program has not latched-up, bypassing important safety thresh- olds. If the Program has latched-up, the microproces- sor initiates a safety shutdown and displays WATCH- DOG – SOFTWARE REBOOT message. JOHNSON CONTROLS...
LED Indicators When power is applied to the OptiView™ Control Cen- ter, both the red (CR18 - Fail) and green (CR17 - Pass) LED's simultaneously illuminate for 1 second, then the Boot-up process begins in the following sequence: JOHNSON CONTROLS...
(CM-2 Current Board for Electromechani- Peak Motor Current cal starter or Style A Solid State Starter Logic Board). phase A, B, C line voltage Refer to the appropriate section of this manual for detailed explanation of each board. JOHNSON CONTROLS...
Page 33
I/O Board is converted to a logic low (less than 1VDC). A 0VAC input to the I/O Board is converted to a logic high (more than 4VDC). Refer to SECTION 5 - I/O Board of this manual for details of the I/O Board. JOHNSON CONTROLS...
Page 34
2 of the flow sensor. Then connect a voltmeter from • CR15 TX3 – COM3 serial port transmit data. Microboard J7-14 (evaporator) or J7-16 (condenser) to • CR14 RX3 – COM3 serial port receive data. Microboard TP1(ground). JOHNSON CONTROLS...
Page 35
031-02430-001 lists the required program jumper con- figuration for each display. Also, a label attached to the display mounting plate lists the required program jumper configuration for that display. The position of program jumper JP2 determines whether the supply voltage is +5VDC or +3.3VDC. JOHNSON CONTROLS...
JP24 to accept these inputs in either 0 to 10VDC, 2 to 10VDC, 0 to 20mA or 4 to 20mA form. Refer to Pro- gram Jumper configurations and SECTION 21 - RE- MOTE SETPOINTS of this manual for details of the Remote setpoints. JOHNSON CONTROLS...
Page 37
FORM 160.54-M1 SECTION 3 - MICROBOARD 031-01730-000 LD07776 FIGURE 10 - MICROBOARD 031-01730-000 JOHNSON CONTROLS...
SECTION 3 - MICROBOARD 031-01730-000 + 12VDC + 12VDC VOLTAGE + 5VDC (ANALOG) FROM POWER + 5VDC (DIGITAL) SUPPLY + 5VDC VOLTAGE + 3.3VDC *REV "E" and later boards only. -12 VDC LD09564 FIGURE 12 - MICROBOARD (031-01730-000) POWER SUPPLY TEST POINTS JOHNSON CONTROLS...
JP5 - Display backlight power. Determines the power input on J22-1. supply voltage applied to the Display Backlight Pins 1-2: Allows a 0 to 20mA or 4 to 20mA Inverter Board. input on J22-2. Pins 2-3: Not Used. JOHNSON CONTROLS...
Page 41
IN: Mod A - Old style with Logic Board mount- microboard adjacent to the program jumper. ed in OptiView™ Control Center. Not used on YK Chiller applications. OUT: Mod B - New style with integrated Log- ic/Trigger Board mounted Starter cabinet. JOHNSON CONTROLS...
OFF: Disables anti-recycle timer. Chiller TB1-34 Liquid Line, TB1-61 Oil Return and can be started at the completion of System Vent Line connected in parallel, TB1-62 High Coastdown, regardless of how long the chiller Speed Thrust. had been running. JOHNSON CONTROLS...
2. The position of Program Jumpers JP7 and JP8 determine the output at J6-7; In = Variable Voltage; Out = Variable Resistance. Refer to Program Jumper Listing for applications. 3. Potentiometer is actually an integrated circuit that is the electrical equivalent of a 10KΩ potentiometer. FIGURE 13 - MICROBOARD LAMP DIMMER CIRCUIT JOHNSON CONTROLS...
1. Microboard Program Jumper JP27 determines whether COM 4A or 4B can be used. 1 and 2 - 4A, 2 and 3, 4B. 2. J15-4 Loop-Around Test IN. J15-5 Loop-Around Test OUT. Refer to FIGURE 88 for details. FIGURE 14 - MICROBOARD SERIAL DATA COMMUNICATIONS PORTS JOHNSON CONTROLS...
2. Applies to Flash memory card version C.MLM.01.07.xxx and later. Program Jumpers JP21 and JP22 must be on pins 2-3 on style F and later chillers equipped with factory-mounted thermal-type flow sensors. FIGURE 15 - CONFIGURABLE ANALOG AND REMOTE SETPOINT INPUTS JOHNSON CONTROLS...
Page 46
FORM 160.54-M1 SECTION 3 - MICROBOARD 031-01730-000 THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
TP3. It is applied to a +3.3VDC regula- OptiView™ Control Cente tor, +2.5VDC regulator and used directly by the mi- Commercial chiller croboard circuits as the Vcc voltage. The outputs of these regulators are applied to Microboard circuits and JOHNSON CONTROLS...
It contains the Safety and Cycling memory storage device that is programmed with the shutdown thresholds (non-changeable) and display chiller operating program. The program card part num- screen messages and graphics. ber for YK chillers is 031-02474-001 and is available JOHNSON CONTROLS...
Page 49
28-pin socket. Program Jumper JP14 trol revision level. The version is as follows: is a non-removable (soldered) wire jumper that con- nects DC power to the appropriate pin on the BRAM for 32KB operation. JOHNSON CONTROLS...
Page 50
The The Program Switches are miniature switches that are Watchdog circuit is a timer that times-out if not given placed in either the ON or OFF position. a reset pulse within its time-out period (1 to 2.25 sec- JOHNSON CONTROLS...
Motor Current (%FLA) Starter model/ Current Phase C Phase B Phase A Phase A Phase B STYLE A Phase C SOLID STATE voltmeter limit motor motor motor line line line voltage STARTER current current voltage voltage range command current JOHNSON CONTROLS...
Page 52
J15-2. Between June 2006 and March 2007, new production VSD communicate with Microboard 031- Refer to Figure 21 on Page 67 and SECTION 13 - 02430-001 using the same interface/protocol. ADAPTIVE CAPACITY CONTROL Board for details of the variable speed drive interface. JOHNSON CONTROLS...
Page 53
Refer to SECTION Refer to SECTION 18 - COMMUNICATIONS of this 20 - TEMPERATURE THERMISTORS of this manual. manual. Included are tables to convert the expected output volt- age for any temperature applied to the thermistor. JOHNSON CONTROLS...
Page 54
A green RX LED illuminates as data is received from another device. The RS-232 voltages are industry standard +5 to +25VDC and -5VDC to -25VDC logic levels. The RS-485 voltages are indus- JOHNSON CONTROLS...
Page 55
The Lamp Dimmer is an integrated circuit that the drive signals are accompanied by a clock and hori- is the electrical equivalent of a 10K ohm potentiometer zontal and vertical sync signals. JOHNSON CONTROLS...
1. Standard – Contacts open at completion of System Coastdown after all shutdowns except LEAVING CHILLED LIQUID – LOW TEMPERATURE. On this shutdown, they remain closed, causing the pump to continue to run while the chiller is shutdown. JOHNSON CONTROLS...
Page 57
Fixed Speed Oil Pump. A de- Variable Speed Drive applications, used when the scription of the two Oil Pumps is as follows: microboard is interfaced to the VSD via the ACC Board. On Style B Liquid Cooled Solid State JOHNSON CONTROLS...
Page 58
Motor Node ID setpoint. Then set the Mod- sition will be shown on respective screens when En- bus Address of the Logic/Trigger Board 031-02505 abled; not shown when Disabled. to 1 by setting Switch SW1 Position 1 to ON with all other positions OFF. JOHNSON CONTROLS...
Page 59
C.OPT.01.23.307 and later) – Allows the • Style B Liquid Cooled Solid State Starter (LC- Heat Pump Duty to be enabled or disabled. SSS) Modbus applications. A summary of the differences between 031-02430-000 and 031-02430-001 Microboards are shown in the fol- lowing table: JOHNSON CONTROLS...
When transferring a 32KB BRAM from 031-02430– Program cards can be re-programmed with the latest 000 Board to 031-02430–001 board - applications program version. other than MV SSS, MV VSD and VSD Modbus ap- JOHNSON CONTROLS...
Download the program as follows: cedure, “Er” displayed. During the Programming procedure, “Pr” is displayed. During the Verifying 1. Remove power to OptiView™ Control Center. procedure, “Ch” is displayed. 2. Remove protective cover from Microboard con- nector U33. JOHNSON CONTROLS...
OFF – Disables diagnostics. Enables normal Pins 2-3: Factory mounted condenser Thermal chiller operation. type flow sensor (new production chillers prior to June 2009). SW1-4 – Not used. JP23 – Remote Current Limit setpoint (J22) type. Configures Analog Input for 0 to 10VDC, 2 to 10VDC, 0 to 20mA or 4 to 20mA. JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 4 - MICROBOARD 031-02430-000 AND 031-02430-001 BRAM BIOS EPROM PROGRAM SWITCHES PROGRAM DOWNLOAD CONNECTOR BOOT-UP LED STATUS DISPLAY = Jumpers = Test Points = L.E.D. = Switches LD09254a FIGURE 17 - MICROBOARD 031-02430-000 AND 031-02430-001 JOHNSON CONTROLS...
+ 5 VDC (Analog) VOLTAGE (For Transducer and Thermistors) + 5 VDC (VCC) 2.5 VDC VOLTAGE 2.5 VDC J1-1 + 5 VDC 3.3 VDC 3.3 VDC VOLTAGE J1-2 LD09255A FIGURE 19 - MICROBOARD (031-02430-000 AND 031-02430-001) DC POWER SUPPLY TEST POINTS JOHNSON CONTROLS...
2. The position of Program Jumpers JP7 and JP8 determine the output at J6-7; In = Variable Voltage; Out = Variable Resistance. Refer to Program Jumper Listing for applications. 3. Potentiometer is actually an integrated circuit that is the electrical equivalent of a 10KΩ potentiometer. FIGURE 20 - MICROBOARD LAMP DIMMER CIRCUIT JOHNSON CONTROLS...
JP17 as follows: On pins 1 and 2 for RS-485 operation. On Pins 2 and 3 for RS-232 operation. The COM 2 RS-485 port is not present on 031-02430-000 Microboard. FIGURE 21 - MICROBOARD SERIAL DATA COMMUNICATIONS PORTS JOHNSON CONTROLS...
3. Factory mounted evaporator Thermal type flow sensor (new production chillers prior to June 2009) or Leaving Chilled Liquid Temperature Thermistor (chillers equipped with the optional Heat Pump Duty.feature) FIGURE 22 - CONFIGURABLE ANALOG AND REMOTE SETPOINT INPUTS JOHNSON CONTROLS...
2-10 VDC TEMP SETPOINT 0-20 mA / 4-20 mA JP24 REMOTE SETPOINT GND CONNECTIONS LD15436 NOTE: 1. Program Jumper JP21 must be positioned on pins 2-3. FIGURE 23 - CONFIGURABLE ANALOG AND REMOTE SETPOINT INPUTS (HEAT PUMP DUTY) JOHNSON CONTROLS...
Jumpers JP10 through JP12 must be positioned on pins 2-3 and software version C.OPT.01.21.307 (and later) is required. On new production chillers prior to June 2009, the Thermal type flow sensors are connected to Microboard J7 (Refer to Figure 22). FIGURE 24 - LOW VOLTAGE DIGITAL INPUTS JOHNSON CONTROLS...
Variable Speed Drive applications. The High Pres- sure safety switch “HP”, must be closed and the RUN The coils of these devices operate on 115VAC and Switch “1SS” must be in the Run position. therefore cannot be directly connected to the mi- JOHNSON CONTROLS...
This actuator operates from remain closed during shutdown, when a chiller restart 24VAC. As described previously in this section, Triacs JOHNSON CONTROLS...
Page 73
C.MLM.01.07.xxx or keypad COMPRESSOR switch is placed in the Stop - later version)) (TB1-64/17) Reset (O) position. On cycling shutdowns, the contacts will close when the cycling condition clears. On safety Contacts operate the same as K15. JOHNSON CONTROLS...
Page 74
K18 - Compressor Motor Starter (TB5-22/25) K13 - Compressor Motor Starter (start) Run Status (TB2-35/36) (TB1-6/16) Contacts operate the same as K14. Contacts close coincident with the beginning of Sys- tem run. They remain closed for 0.2 seconds and then open. JOHNSON CONTROLS...
TB1- 61 OIL RETURN SOLENOID (ALL STYLES) (LIQUID LINE SOLENOID - TB1 - 1 (Style D and later chillers) J-COMPRESSOR ONLY) VENT LINE SOLENOID (Style C and earlier chillers) LD09042 FIGURE 29 - J1 I/O BOARD DIGITAL OUTPUTS JOHNSON CONTROLS...
Page 79
Drive Applications). 3. Chillers equipped with P compressors and all style "F" and later chillers use a different High Pres- sure (HP) Switch and associated interface than other compressor applications. FIGURE 29 - J1 I/O BOARD DIGITAL OUTPUTS (CONT'D) JOHNSON CONTROLS...
Page 80
CLOSE TB1-163 FIELD 115VAC REFRIGERANT TB1-161 LEVEL CONTROL ACTUATOR (BELIMO) REFRIGERANT J1-29 TRIAC LEVEL CONTROL DRIVER OPEN TB1-162 24VAC REFRIGERANT J1-28 TRIAC LEVEL CONTROL DRIVER CLOSE TB1-163 115VAC LD09567 FIGURE 29 - J1 I/O BOARD DIGITAL OUTPUTS (CONT'D) JOHNSON CONTROLS...
Imbedded in each window of the pixel is a transistor, is approximately 16 milliseconds. The next VSYNC the conduction of which determines the amount of light pulse causes the above cycle to repeat. that will pass through the window. The conduction of JOHNSON CONTROLS...
Page 82
Displays stocked for Service replacement are a Microboard section and the Display Interface Board result of that same agreement. Therefore, the Display section that follows. received for service replacement may be by a differ- JOHNSON CONTROLS...
4. Using small Phillips screwdriver, remove lamp wires to the display with power applied retaining screw. will damage the display!!! 5. Grasp lamp AC power connector and gently pull until lamp housing is completely removed from the Display. JOHNSON CONTROLS...
1. Slide new lamp into Display from left to right un- til lamp housing is fully inserted. 2. Secure lamp with lamp retaining screw. 3. Connect lamp AC power connector to Backlight Inverter Board. 4. Apply AC power to OptiView™ Control Center. LD04062 FIGURE 30 - DISPLAY MOUNTING JOHNSON CONTROLS...
ENABLE PERIOD PERIOD PERIOD 39.72 NS 640 CLKS NOTES: (25.18 1. BP = Back Porch = 4-48 CLKS MHz) 2. FP = Front Porch = 2-16 CLKS LD04066 FIGURE 34 - LIQUID CRYSTAL DISPLAY TYPICAL CONTROL SIGNAL TIMING JOHNSON CONTROLS...
(white/GND side) HOLE LOCKING TAB WIRE (pink/HOT side) DIRECTION A DIRECTION B DIRECTION C LD04067 FIGURE 35 - DISPLAY (SHARP LQ10D367/368) LAMP REPLACEMENT SCREW FOR LAMP REMOVAL LD14075 FIGURE 36 - DISPLAY (SHARP LQ104V1DG61 (031-02886-000) AND LG LP104V2-W (031-02046-000)) JOHNSON CONTROLS...
Page 88
FORM 160.54-M1 SECTION 6 - LIQUID CRYSTAL DISPLAY THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
LG Semicon LP104V2-W (031-02046-000) • Display Interface Board 031-01765-001 PID0 – IN (GND) Display Applicability: PID1 – OUT (VCC) LG Semicon LP104V2-W (031-02046-000) PID2 – OUT (VCC) P30 – OUT (Open) PID3 – OUT (VCC) P31 – OUT (Open) JOHNSON CONTROLS...
Page 90
• Display Interface Board 031-02887-000 face Board. The value of VCC is either +5VDC or Display Applicability: +3.3VDC, as determined by the position of Program Jumper JP2 on the microboard. SHARP LQ104V1DG61 (031-02886-000) J1-30 – (VCC) J1-31 – (GND) JOHNSON CONTROLS...
When the Backlight Enable signal is +5VDC, the high croboard provides the Backlight Enable signal. This voltage signal is applied to the lamp. When the Enable signal turns the lamp ON and OFF. Some manufactur- is 0VDC, the high voltage is removed from the lamp. JOHNSON CONTROLS...
Display and rocker switch openings and a key in that column and row is pressed. For example, apply the keypad to the door. if at the time row 4 is being driven low, if column 3 JOHNSON CONTROLS...
Analog circuits and is labeled as the +5VDC (Analog) supply. It is also routed to all Pressure Trans- ducers, Temperature Thermistors, Proximity probe and Motor Controller Board (CM-2, Mod A Solid State Starter Logic Board or VSD ACC Board). JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 10 - POWER SUPPLY FIGURE 44 - POWER SUPPLY – DC POWER DISTRIBUTION (REFER TO OPTIVIEW™ CONTROL CENTER WIRING DIAGRAM FOR WIRE CONNECTIONS) JOHNSON CONTROLS...
Electro-Mechanical Starter present; UP for plied to potentiometer R8. This is factory adjusted Y-delta or 57% Autotransformer starters, DOWN for (field adjusted on service replacements) to illuminate all other starters. the 105% CURR indicator (CR6) when the compressor JOHNSON CONTROLS...
FLA, the microboard applies a close signal to the PRV calibrated on CM-2 until the motor current decreases to 102% FLA. While board to be +4.0VDC Current Limit is in effect, MOTOR - HIGH CUR- at 100% FLA. RENT LIMIT is displayed. JOHNSON CONTROLS...
Microboard 031-02430-001, equipped with the 128K displays LCSSS INITIALIZATION FAILED on the BRAM and software C.OPT.01.15.xxx (or later) is re- System Details line of the OptiView™ Control Center quired for this application. Microboard Program Jump- display. The microboard will continue to establish com- JOHNSON CONTROLS...
Page 108
On new production chillers after mid 2008, Microboard under LAST TEN FAULTS. Refer to Operation Manual 031-02430-001 COM 2 (J13) serial port communicates (Form 160.54-O1) for description of all Cycling and with Logic/Trigger Board 031-02505 (J14) using RS- Safety shutdown messages. JOHNSON CONTROLS...
Page 109
Full Load Amps (FLA) of the chiller, as listed Logic/Trigger Board initiates a cycling shutdown and on the SALES ORDER Screen. Each starter mod- displays LCSSS - HIGH SUPPLY LINE VOLTAGE or el has a permissible range over which this setpoint can be programmed as follows: JOHNSON CONTROLS...
Page 110
Logic/Trigger Board, by the value decreases to less than or equal to 98% of the Current programmed for the Full Load Amps setpoint. The Limit setpoint. message % FULL LOAD AMPS is displayed on the JOHNSON CONTROLS...
JUMPER BETWEEN NO. 7 AND 8 PINS LOGIC P1 / J1 Board PLUG INDICATOR CONN. LED’S 24672A R3 R2 R1 START OVERLOAD RESET RESISTORS CURRENT POT CURRENT POT PUSHBUTTON (SWI) FIGURE 51 - SOLID STATE STARTER LOGIC BOARD JOHNSON CONTROLS...
Page 113
Table 9 on Page 114. Rotation/Loss or Trigger Board Out of Lock (OOL) LED illuminates and remains illuminated until manu- ally reset with the S1 RESET switch. The chiller will automatically restart when the contacts close. JOHNSON CONTROLS...
Phase A Compressor Motor Current. 0 to +5VDC spanning range in address 0 above. Phase B Compressor Motor Current. 0 to +5VDC spanning range in address 0 above. Phase “C” Compressor Motor Current. 0 to +5VDC spanning range in address 0 above. JOHNSON CONTROLS...
Condenser Pressure Differential (head) that exists bus. If Modbus is selected, the Motor Node ID setpoint when each surge occurs. must be set to match the setting of the VSD Logic Board Modbus Address Switch SW3. They must be both set to “1”. JOHNSON CONTROLS...
Page 118
Board. The ACC Board returns both the VSD Logic each of these commands. If a response is not received Board’s response and the Harmonic Filter’s response to to 10 consecutive commands, a cycling shutdown is the microboard. performed and VSD – SERIAL COMMUNICATIONS JOHNSON CONTROLS...
Page 119
• Pre-rotation Vanes position • Input Power KW • Surge count • KWH The compressor motor speed can be controlled either • 100% Job FLA manually in Manual Mode or automatically in Auto • DC Link Voltage Mode. JOHNSON CONTROLS...
Page 120
80% but less than 98%FLA. OptiView™ display as 0% when fully closed, 100 • 0.2Hz every 19 seconds if none of the above con- % when fully open and whole percentage points ditions are present. in between. JOHNSON CONTROLS...
Page 121
Surge Detected by the Delta P method must have all of bility by comparing the Leaving Chilled Liquid the following conditions occur within 5 seconds to be Temperature to the Leaving Chilled Liquid Tem- considered a valid surge: perature setpoint to arrive at a rate of change value. JOHNSON CONTROLS...
Page 122
1.0Hz but the surge is not plotted on the Surge Map fied Service technicians as a method of plotting a surge since these conditions would produce an erroneous JOHNSON CONTROLS...
Page 123
0 to 5VDC form. LED’s YM XMT (CR7) • TPD: Harmonic Filter Logic Board 0 to +5VDC and YM RCV (CR6) LED’s illuminate during serial 1200 baud serial data. communications with the OptiView™ Control Center • TPE: Harmonic Filter Logic Board Frame pulse. JOHNSON CONTROLS...
This logic shall be in tarily illuminates and the “ACC Surge Count” incre- effect during the entire initial ramp and take action as ments (The “Surge Avoidance Surge Detected” LED is many times as necessary. shown for reference only. It momentarily illuminates JOHNSON CONTROLS...
Page 125
ACC current limiting shall not be allowed to de- way to clear it is to clear the BRAM. To prevent this crease the frequency below the mapped point. from happening, this value is no longer programmable. It is now always set to 7000. JOHNSON CONTROLS...
FIGURE 54 - SERIAL COMMUNICATIONS INTERFACE – YORK PROTOCOL ADAPTIVE CAPACITY MICROBOARD VSD LOGIC BOARD CONTROL BOARD 031-02430-001 031-01782 031-01433 COND PRESSURE 031-02077 031-02506 EVAP PRESSURE COM 5 OPTO-COUPLE COM 2 RS-485 POSITION LD12568 FIGURE 55 - SERIAL COMMUNICATIONS INTERFACE – YORK PROTOCOL JOHNSON CONTROLS...
This value remains the Reference Position until the compressor is rebuilt, whereupon the calibration proce- dure must be repeated to establish a new Reference Posi- tion. Since this Reference Position value is stored in the BRAM (U52) memory device on the microboard, field JOHNSON CONTROLS...
Page 132
Probes. The Probe differences vary with the vin- tage. The differences are listed in Table 10 on Page 133. For service replacement, refer to part number listed in Renewal Parts – OptiView™ Control Center (Form 160.54-RP1) or the unit renewal parts manual. JOHNSON CONTROLS...
The probe is connected to the electronics module with a coaxial cable. Refer to Figure 60 on Page 135 for parts breakout of probe assembly 025-40496-000. JOHNSON CONTROLS...
1. +24VDC Reference for “Proximity probe - Low Supply Voltage” Cycling Shutdown. 2. CM-2 Board, Solid State Starter Logic Board or Adaptive Capacity Control Board as determined by the Starter Application. FIGURE 59 - PROXIMITY PROBE INTERFACE – PROBE PART NUMBER 025-35900-000 AND 025-35900-001 JOHNSON CONTROLS...
5. When replacing previous probe versions with this probe, use the existing cable and retrofit kit 364-51806-000, consisting of: 025-40496-000 probe assembly (Refer to note 4) 025-37805-000 DIN connector 028-12209-000 O-ring 035-21458-000 instruction drawing FIGURE 60 - PROXIMITY PROBE INTERFACE – PROBE PART NUMBER 025-40496-000 JOHNSON CONTROLS...
Page 136
FORM 160.54-M1 SECTION 14 - PROXIMITY PROBE 2.0" + 24VDC PROBE LD06510 YORK PART NUMBER 025-30961-000 025-30961-000 2.0" + 24VDC PROBE LD05529a YORK PART NUMBER 025-35900-000 025-35900-000 and 025-35900-001 FIGURE 61 - PROXIMITY PROBE JOHNSON CONTROLS...
15 to 25 PSIG. One side of these con- CONTROL CENTER COMPRESSOR BOARD LD06866 FIGURE 62 - HIGH SPEED THRUST BEARING LIMIT SWITCH – INTERFACE JOHNSON CONTROLS...
Some sensors are equipped with Upon entering chiller Pre-lube, the Refrigerant adjustable potentiometers, while others are equipped Level close output is energized for the length of with pushbuttons that are used to calibrate the sensor. JOHNSON CONTROLS...
Page 140
Level setpoint in a recurring period of time called • ZONE 2 a Level Control Period. At the end of each Level Con- trol Period, the Proportion error and Rate of Change • ZONE CONTROL OFF (if chiller shutdown) JOHNSON CONTROLS...
Page 143. The description of the operation of both ac- ror is to the Limit; close yields larger influence, further tuators is in the SECTION 5 - I/O Board of this manual. yields smaller influence. To establish the response to the JOHNSON CONTROLS...
Coastdown period, it operates it over the same frequen- during the last 10 seconds of system pre-lube cy range to maintain the pressure to the programmed or during the first 15 seconds of system run. oil pressure setpoint. JOHNSON CONTROLS...
Oil Pressure setpoint and the actual be used to monitor the actual oil pressure and the speed oil pressure is less than plus or minus 6 PSID, the fre- command. quency is increased or decreased 0.5Hz to increase or JOHNSON CONTROLS...
To prevent overheating the oil in the event of an OptiV- all Style "F" (and later) chillers iew™ Control Center failure, thermostat 1HTR opens at 180°F. OIL PUMP VSD 28782A FIGURE 66 - OIL PUMP VARIABLE SPEED DRIVE (VSD) JOHNSON CONTROLS...
COM 4B communications port. Refer to SECTION 33 - DIAGNOSTICS AND TROUBLE- SHOOTING of this manual. E-LINK GATEWAY G TX G RX TO BAS + 12VDC RS-485 LD06511 MICROBOARD FIGURE 69 - E-LINK GATEWAY INTERFACE BLOCK DIAGRAM JOHNSON CONTROLS...
Page 150
FORM 160.54-M1 SECTION 18 - COMMUNICATIONS THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
The differential between the sump and TROUBLESHOOTING of this manual. pump oil pressure transducer outputs during a 3 second period beginning 10 seconds after the start of the Sys- tem Pre-lube period are compared to determine the off- JOHNSON CONTROLS...
P = (17 x V) - 2.5 P + 37.5 P = (75 x V) - 37.5 V = VOLTS DC P = PRESSURE (PSIG) LD09969A V = VOLTS DC P = PRESSURE (PSIG) LD09569a FIGURE 70 - PRESSURE TRANSDUCERS JOHNSON CONTROLS...
If any of the displayed pressures do not appear to be this voltage at the input to the microboard and converts correct, refer to SECTION 33 - DIAGNOSTICS AND it to a temperature value. TROUBLESHOOTING of this manual. JOHNSON CONTROLS...
Current Limit setpoint setpoint varies linearly from 100% to 30% FLA as the to 100% and the Leaving Chilled Liquid Temperature input varies from 0 to l0VDC. This input will only be setpoint to the locally programmed Local BASE value. JOHNSON CONTROLS...
Page 178
This input will only be accepted in Digital various inputs as follows: Remote Mode. Calculate the setpoint for various pulse widths as follows: Setpoint (%) = 100 – (mA x 3.5) Setpoint (%) = 100 – [(pulse width in seconds – 1) x 7] JOHNSON CONTROLS...
Reset Temperature Range setpoint is programmed is not used as a “base” in this application. for 10°F and the Local Leaving Chilled Liquid Tem- perature setpoint is programmed for 40°F, the setpoint would be set to 45°F as follows: JOHNSON CONTROLS...
Page 180
= 43.8°F Offset (°F) = (mA–4)(Remote Reset Temp Range) 0 to 20mA As shown in Figure 15 on Page 45, connect input to Setpoint (°F) = Local Setpoint + Offset Microboard J22-4 (signal) and J22-5 (GND). A 0mA JOHNSON CONTROLS...
10°F and the Local Leaving Chilled for the Leaving Chilled Liquid Temperature setpoint Liquid Temperature setpoint is programmed for 40°F, inputs as explained above. The Leaving Condenser the setpoint would be set to 44°F as follows: JOHNSON CONTROLS...
Page 182
As shown in Figure 12, the input is connected to Range setpoint). Select Digital Remote Mode. The re- Microboard J22-3 (signal) and J2-5 (GND). A 2VDC lay contact closure should occur at least once every 30 signal produces a 0°F offset. A 10VDC signal produces JOHNSON CONTROLS...
Page 183
E-Link Gateway. Select ISN Remote Mode. not to exceed once every 70 seconds. The setpoint is calculated as follows: Offset(°F) = (PW – 1)(Remote Reset Temp Range) Where PW = Pulse Width in seconds Setpoint (°F) = Local Setpoint - Offset JOHNSON CONTROLS...
Page 184
FORM 160.54-M1 SECTION 21 - REMOTE SETPOINTS THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
“Temperature Differential (Leaving will be closed at 10 minute intervals after the Hold Chilled Liquid Temperature minus setpoint)” on the Period has elapsed. Refer to Hold Period above. hot gas screen. The surge events it reacts to are detect- JOHNSON CONTROLS...
• If Hot gas valve position is greater than 50%, it is as it does in a standard YK chiller without Heat Pump driven open another 10%. There will be no valve ability. However, in Heating Mode, Hot gas operation response to surge events in the next 2 minutes. JOHNSON CONTROLS...
Manual control has priority over Minimum Load serial port using Opto-22 protocol. It is compatible Override, Variable Speed Drive Override and Auto- with Microboard 031-01730-000 and 031-02430-000/- matic Control. 001, equipped with any software version. Refer to Fig- ure 71 on Page 189. JOHNSON CONTROLS...
Service Replacement present, it is connected to this board at P1. If I/O Replace the defective board with the same part number Board 031-02895-000 is present, it is connected board. This prevents any compatibility issues. to the microboard J7. JOHNSON CONTROLS...
Pre-Rotation Vanes Load Inhibit still oc- Low Evaporator Pressure Safety thresholds (R22 – 54.3 curs at the same thresholds as with normal operation; PSIG, 29.6°F) (R-134a – 25.0 PSIG, 28.7°F) are used. inhibit at 56.2 PSIG (R22) and 27.0 PSIG (R-134a). As JOHNSON CONTROLS...
Page 192
• Minimum Leaving Chilled Liquid setpoint - 36.0°F Note 1: The freeze threshold evaporation saturation • If the Leaving Chilled Liquid Temperature temperature is 32.0°F on Flash memory card version setpoint is greater than or equal to 38.0°F: C.MLM.01.01 (and earlier). JOHNSON CONTROLS...
The parameters displayed drive is running at maximum frequency). If equipped on this screen vary according to the software version with software version C.OPT.01.18.307 or earlier, the and compressor motor type as noted below. JOHNSON CONTROLS...
SURGE PROTECTION continue to run under the same conditions displaying – EXCESS SURGE is displayed. WARNING – EXCESS SURGE DETECTED. This message will be displayed until manually reset with the WARNING RESET key in OPERATOR access level. JOHNSON CONTROLS...
VSD output frequency is at maximum. Software version C.MLM.01.09.xxx (and later) or C.OPT.09.301 (and later) – The Extended Run Mode, Shutdown Mode and EXCESS SURGE WARNING message will not be implemented unless the VSD out- put frequency is at maximum. JOHNSON CONTROLS...
Page 196
FORM 160.54-M1 SECTION 24 - SURGE PROTECTION THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
Hot gas valve closure. The VGD is held in last posi- VOLTAGE and is input to the microboard where it is tion until one of the following occurs: compared to the Low Limit and High Limit setpoint JOHNSON CONTROLS...
Page 198
VGD is closing. count can be reset using an ADMIN access level. The ac- cumulated time the Stall Detector Board output voltage is greater than the HIGH LIMIT threshold is displayed on the VGD Screen as VGD TIME. JOHNSON CONTROLS...
Control Status displays PRV POSITION played. The VGD is held in the open position until the OVERRIDE. warning is manually cleared. It can be cleared after the Stall Detector Voltage returns to less than two times the JOHNSON CONTROLS...
Probe Wait setpoint RIDE is displayed as Control Status. interval. • Probe Wait (0.5-15 minutes; default 10) – Speci- fies how long the VGD control remains in the Stall Waiting or Surge Waiting states before enter- ing the Probing state. JOHNSON CONTROLS...
Check outputs an analog voltage (displayed as STALL the part number of the replacement transducer and make DETECTOR VOLTAGE on the VGD Screen) connections at the transducer connector as follows: that represents the magnitude of stall noise pres- JOHNSON CONTROLS...
Hot Gas Valve Open Detect Stall Hot Gas Valve Open HOT GAS OVERRIDE Action Arrow Legend Hold VGD Stall Surge Hot Gas Valve LD15438 NOTES: 1. Software version C.OPT.01.23.307 (and later), FIGURE 74 - VARIABLE GEOMETRY DIFFUSER STATE DIAGRAM JOHNSON CONTROLS...
Page 204
FORM 160.54-M1 SECTION 25 - VARIABLE GEOMETRY DIFFUSER THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
The respective LED illuminates when the 120VAC at the microboard, the microboard’s RX3 (CR16) il- input is present. Otherwise, it is extinguished. The -000 luminates. board is component populated for 2 inputs. The -001 board is populated for 6 inputs. JOHNSON CONTROLS...
I/O Board and key to select the desired output, then use the numeric transmitted to the microboard, is displayed as ANA- keys to set it to the desired value. LOG INPUTS. LD14349 FIGURE 83 - I/O BOARD (031-02895-XXX) JOHNSON CONTROLS...
If Head Pressure Control is played on this screen as described below. also enabled, the Head Pressure parameters appear on the HEAT RECOVERY Screen (there is no separate HEAD PRESSURE CONTROL screen in this configu- ration). JOHNSON CONTROLS...
NO water flow in the heating condenser, valve control will automatically switch over to the Head Pressure Control. 2. The chiller could be equipped with either paddle/differential pressure (120VAC) type or Thermal Type (+5VDC) flow switches. Each Type must be connected as shown. LD14238 FIGURE 84 - HEAT RECOVERY BLOCK DIAGRAM JOHNSON CONTROLS...
Hot Water Setpoint Analog PID Control Analog Output Error Control Output Output Conditioning (0-10V, Leaving Heating (0.0–100.0%) 10-0V, Condenser Water 4-20mA [2-10V], Temperature 20-4mA [10-2V]) Type Output (0-10V, (Direct, (PID Gains) 4-20mA) Reverse) FIGURE 85 - PID CONTROLLER DIAGRAM JOHNSON CONTROLS...
Not Active Not Active Head Pressure Head Control Active Pressure Control PID Control Mode Enabled? is Head Pressure Head Pressure Control Not Active PID Control Mode is Inactive Valve Output = 0% FIGURE 86 - HEAT RECOVERY FLOW DIAGRAM JOHNSON CONTROLS...
YORK Talk III Comms Setpoint (GPIC List) Offset added to local Hot Water Setpoint Remote Hot Water Analog Analog Input 0V = -0°F offset, 10V = -20°F offset Setpoint Offset 4mA = -0°F offset, 20mA = -20°F offset JOHNSON CONTROLS...
Page 216
FORM 160.54-M1 SECTION 27 - HEAT RECOVERY THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
MICROBOARD 031-02430-000 BOARD 031-02430-001 031-02895-000 SERIAL COMMS 4/12 RS-485 COM 3 3/11 VALVE POSITIONING HEAD PRESSURE 18 21 CONTROL VALVE 0-10VDC or 4-20mA EVAPORATOR TRANSDUCER CONDENSER TRANSDUCER LD14237 FIGURE 87 - HEAD PRESSURE CONTROL BLOCK DIAGRAM JOHNSON CONTROLS...
Setpoint Analog PID Control Analog Output Error Control Output Output Conditioning (0-10V, (0.0–100.0%) Head Pressure 10-0V, (Delta P) 4-20mA [2-10V], 20-4mA [10-2V]) Type Output (0-10V, (Direct, (PID Gains) 4-20mA) Reverse) FIGURE 88 - HEAD PRESSURE CONTROL FLOW DIAGRAM JOHNSON CONTROLS...
Reverse chart in SECTION 27 - HEAT RECOVERY . 4 to 20mA Direct 4mA (2V) 20mA (10V) 4 to 20mA Reverse 20mA (10V) 4mA (2V) Remote Head Pressure Setpoint This setpoint cannot be set from a remote input. JOHNSON CONTROLS...
Page 220
FORM 160.54-M1 SECTION 28 - HEAD PRESSURE CONTROL THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
OptiView™ reboot time. This provides the access level. However, once disabled, it requires an fastest possible ability to start or restart after generator ADMIN password to enable it again, as explained above. or utility power is restored. JOHNSON CONTROLS...
Page 222
• VSD Start Frequency (60Hz units with quick start enabled equals 30Hz to 45Hz; default 45Hz) (50Hz equals 25Hz to 37.5Hz; default 37.5Hz) - JOHNSON CONTROLS...
30 seconds after coastdown has completed, the fol- begins. No Pre-lube occurs. lowing control returns to standard control: • Oil Pressure more than 25PSID • Chilled Liquid Pump control returns to standard • VSD has completed Precharge • PRV control returns to standard JOHNSON CONTROLS...
Standard when LCHLT less than Ac- Slow Ramp-up of Speed Setpoint + Quick Pulldown Setpoint tive LCHLT Setpoint + Quick Pulldown Offset OR when Run Time more than Setpoint Offset OR when Run Time > Pulldown Override Time Pulldown Override Time JOHNSON CONTROLS...
Page 225
This fault is currently only Normal operation turns the chilled liquid pump off at active during pre-lube and run. It shall not cause a shut- the end of coastdown. When Quick Start is ENABLED down during coastdown or while not running. JOHNSON CONTROLS...
Page 226
• LCHLT less than Active LCHLT setpoint + Quick TB5-23 to TB5-22. Pulldown Setpoint Offset • Command Frequency equals Maximum VSD Fre- quency • Run Time more than Pulldown Override Time Once one of these conditions is met, ACC control shall return to standard. JOHNSON CONTROLS...
HEAT PUMP Screen is accessible from Sets the range over which an analog signal (0 to 20mA, the CONDENSER Screen. 4 to 20mA, 0 to 10VDC or 2 to 10VDC) in Analog Re- mote Mode or a PWM signal (1-11 seconds) in Digital JOHNSON CONTROLS...
Chilled Liquid Temperature in Heating Mode, if the Heat Pump restart until the heating load has increased. Leaving Chilled Liquid Temperature decreases to the Requires OPERATOR or higher access level. JOHNSON CONTROLS...
0% when this temperature falls back to 105°F. All other aspects of Hot gas control remain unchanged in Heat- ing Mode. Refer to SECTION 22 - Hot gas bypass in this manual for details of the hot gas bypass operation. JOHNSON CONTROLS...
3. Input resets Leaving Chilled Setpoint when heat pump operational mode setpoint is set to "Cooling" Input resets Leaving Condenser Setpoint when heat pump operational mode setpoint are set to "Heating". FIGURE 89 - HEAT PUMP DUTY BLOCK DIAGRAM JOHNSON CONTROLS...
FORM 160.54-M1 SECTION 31 - MOTOR MONITORING MOTOR MONITORING Board BASIC BLOCK DIAGRAM LD15001 FIGURE 91 - MOTOR MONITORING BOARD BASIC BLOCK DIAGRAM JOHNSON CONTROLS...
The board is shown in Figure 90 on Page 231. 4=Off 8=Off The board does not contain a separate program stor- age device. The boards are programmed at the time of manufacture, and the program cannot be changed in the field. JOHNSON CONTROLS...
6. When thermistors are used for Winding Temperatures, they can be connected to the Motor Monitoring Board TB1 (see Note 1) or the VSD and the temperature values transmitted via existing VSD to Microboard Serial Communications. LD15000 FIGURE 92 - MOTOR MONITORING BLOCK DIAGRAM JOHNSON CONTROLS...
Page 235
TOR SETPOINTS Screen. Program Jumper JP1 configuration, the input is low when the input must always be removed. It is only installed for switch is open; high when closed. Both of these manufacturing testing. inputs have an LED (DI1 and DI2) that illumi- JOHNSON CONTROLS...
This is the default setting. The Motor Moni- Ohm Thermistor. CONFIGURABLE ANALOG INPUTS +5VDC LOAD RESISTOR SELECT FROM PROCESSOR NOTES Phase A thermistor connection shown. Typical of all thermistor inputs. LD15004 FIGURE 93 - WINDING TEMPERATURE – THERMISTORS JOHNSON CONTROLS...
Page 237
266 320°F Refer to Table 23 on Page 243 for RTD resistance/ (default 311). The WINDING HOTSPOT ALLOW- voltage table. Refer to Table 24 on Page 243 for ANCE safety shutdown threshold is programmable over Thermistor resistance/voltage table. JOHNSON CONTROLS...
Monitoring Board to read the sensor inputs at the respective data boxes on the MOTOR SETPOINTS following points: Screen. RTD ANALOG INPUTS NOTES Phase A RTD connection shown. Typical of all RTD inputs. LD15005 FIGURE 94 - WINDING AND BEARING TEMPERATURE – RTD JOHNSON CONTROLS...
Once set, the mi- VIBRATION ANALOG INPUTS GAIN 1:1, 11:1, 21:1 GAIN SELECT FROM PROCESSOR NOTES Shaft end connection shown. Typical of opposite shaft end input. LD15006 FIGURE 95 - BEARING VIBRATION SENSOR JOHNSON CONTROLS...
Page 240
If Vibra- ues manually entered with the VIBRATION SETUP tion Baseline values are established after thresholds SETPOINT key. Normally, the Baseline derived values have been entered with the Vibration Setup setpoint, JOHNSON CONTROLS...
Stop-Reset (O) position. This safety shutdown does not sor inputs. occur when the Motor Vibration Protection setpoint is Digital inputs +24VDC OPT0 COUPLER CLOSE = OK OPEN = TRIP LD15002 FIGURE 96 - MOTOR COOLING COIL LEAK DETECTOR – FLOAT SENSOR JOHNSON CONTROLS...
The optical sensor contains a switch that is connected leak sensor no longer indicates a leak and the COM- between TB7-5 (input) and TB7-6 (GND). With no PRESSOR switch is placed in the Stop-Reset position. leak being detected, the switch closes producing a less JOHNSON CONTROLS...
This password is obtained by contacting the local is displayed momentarily. Johnson Controls Service Office. When requesting this Some safety shutdowns will not permit the chiller to password, supply the “Controls” version of software (available on the DIAGNOSTIC Screen) and the cal- start until a special reset procedure is performed.
RES required to “SSS-Mod A”, “SSS-Mod B” or “MV SSS”, achieve this voltage. Adjust both resistors equally as appropriate. such that the combined resistance equals the cal- culated value. 6. Press ENTER () key. JOHNSON CONTROLS...
Page 247
4 - Microboard 031-02430-000 AND 031-02430- 2. Use ◄ and ► keys to scroll to desired value. 001. Used when the microboard is interfaced to LCSSS Logic/Trigger Board 031-02505 (J14). 3. Press ENTER () key. Microboard can be equipped with either 32K BRAM (031-02431-000) or 128K BRAM (031- 02565-000). JOHNSON CONTROLS...
Page 248
Logic Board is field replaced, field calibration is neces- sary. Logic Board Program Jumper JP5 (300V/600V) 1. Press VOLTAGE RANGE key. must be placed in the appropriate position per the com- 2. Use ◄ and ► keys to scroll to desired value. pressor motor AC power line. 3. Press ENTER () key. JOHNSON CONTROLS...
Page 249
Select COMPRESSOR Screen. on Solid State Starter Logic Board until the 105% FLA LED illuminates. Clockwise in- b. Run chiller and monitor Compressor Motor creases signal level; Counterclockwise de- current on the COMPRESSOR Screen. creases signal level. Tighten locking nut. JOHNSON CONTROLS...
Vari- 1. At the keypad, log in at SERVICE access level able Speed Drive Logic Board. In order to select (unless otherwise noted) using password 1 3 8 0. Modbus, Microboard 031-02430-001 is required JOHNSON CONTROLS...
Page 251
This is the Full Load Amps (FLA) of the chiller as played when the clearing has completed. IM- listed on the SALES ORDER Screen. The microboard PORTANT! – This should not be performed uses the programmed value to perform Current Lim- unless advised by YORK factory Service. JOHNSON CONTROLS...
Page 252
Programmable over the range of AMT (increment amount) key. 0.5°F to 20.0°F (default 1.0°F), 0.5°F to Each press of this key increases the frequency 4.0°F (software version C.OPT.01.22.307 by the programmed Amount (0.1 to 10.0Hz). (and earlier)). JOHNSON CONTROLS...
OptiView™ Control Center door. Using numeric anyone other than a qualified Service technician. keypad keys, enter this value. Only values be- tween 37 and 79 mils will be accepted. 6. Press ENTER () key. JOHNSON CONTROLS...
1 3 8 0. the procedure below. 3. After Coastdown is complete, select Proximity The refrigerant Level Sensor, located in the Condenser, probe CALIBRATE Screen from COMPRES- must be properly calibrated to accurately detect the re- SOR Screen. JOHNSON CONTROLS...
Page 255
Rate Limit Open - 10% to 50% (10%) Screen from the CONDENSER Screen. 5% to 50% (10%) (Flash memory card 3. Press the appropriate key to select the setpoint to version C.MLM.01.06.xxx and later or be programmed. C.MLM.04.02.xxx). JOHNSON CONTROLS...
3. The speed can be increased and decreased in 0.5Hz increments using the RAISE and LOWER Enable/Disable keys. Each time the key is pressed, the frequency is changed 0.5Hz. The Oil Pump Variable Speed Drive Program opera- tion must be enabled. JOHNSON CONTROLS...
Oil when the pressure decreases to 5 PSIG below the pro- Pump for 2 minutes every 24 hours if the chiller has grammed value. Proceed as follows to enter this value: JOHNSON CONTROLS...
Longest allowed pulse is 18 seconds in duration. This selection will ture sensor in the drop leg between the condenser and provide proper operation in most applications. evaporator. If ENABLED with the procedure below, JOHNSON CONTROLS...
The Default value is the recommended value TOR PRESSURE safety shutdown threshold calculation, and should provide proper operation in most applica- as explained in SECTION 23 - SMART FREEZE PRO- tions. However, the setpoint can be programmed to oth- TECTION of this manual. JOHNSON CONTROLS...
Field 1 – Regional phone number label. Default value 1. At the keypad, log in at SERVICE access level is “Johnson Controls North American Parts using password 1 3 8 0. Center Toll Free Number”. 2. Select Hot gas bypass Screen from the COM- Field 2 –...
1. At the keypad, log in at ADMIN access level. Ob- only applicable to chillers equipped with Flash tain ADMIN password from local service office. memory card Version C.MLM.01.01 and later. This password changes daily. 2. Select SURGE PROTECTION Screen from COMPRESSOR Screen. 3. Press CLEAR SURGE COUNT key. JOHNSON CONTROLS...
3. Press CHANGE USER ATTRIBUTES key. The first changeable area is outlined in a green selec- can be used to forward space. tion box. 8. Press ENTER () key. ◄ ► ▲ ▼ 4. Use the keys to move the green selection box to the desired value to be changed. JOHNSON CONTROLS...
• Date and time of change chiller style/compressor combinations are equipped • Access Level and User ID used to make the change differently and have different control requirements. • Old Value Variables include the following: • New Value JOHNSON CONTROLS...
After the selection is made, the program will read the vided connected to the microboard J14 (Refer to Fig- flow sensor input at the selected connection point and ure 23 on Page 69). ignore the other connection points. JOHNSON CONTROLS...
• Motor Monitoring - enable/disable (software ver- Enable/Disable sion C.OPT.01.22.307 and later). If the compressor is equipped with the VGD, it must • Heat recovery-enable/disable (software version be enabled. Otherwise it must be disabled. Use the fol- C.OPT.01.21.307 and later). lowing procedure: JOHNSON CONTROLS...
Page 268
PRV position is 0.3VDC with software version C.OPT.01.22 (and earlier)) to 0.7VDC. Press the START CALIBRATION (Software version C.MLM.01.14.xxx (and later) key to initiate the calibration. The CALIBRA- or C.OPT.01.14.306 (and later)) TION IN PROGRESS and PRV OPENING LED JOHNSON CONTROLS...
CONDENSER – HIGH PRES- the MOTOR Screen in any access level, displays infor- SURE - STOPPED is displayed. The chiller can be mation applicable to this feature. started after the Condenser Pressure decreases to less JOHNSON CONTROLS...
Page 270
DOWN key. recorded when the operator enters his/her initials, name 7. Use the ◄ and ► keys to select Enable or Disable or User ID with the MOTOR LUBE ACKNOWLEDGE as desired per above. key in the above procedure. However, if it is necessary 8. Press ENTER () key. JOHNSON CONTROLS...
6. Use left/right arrow keys to select the desired set- 7. Press the key. ting. Once enabled, the Quick Start setpoints can be changed 7. Press key. using the following procedure. 1. At the keypad, login at SERVICE access level us- ing access code 1380. JOHNSON CONTROLS...
The default setting is line over a 1 hour period while the chiller is running. Disabled. To Enable or Disable the Motor Bearing Vi- To access the MOTOR DETAILS screen: bration Protection feature: JOHNSON CONTROLS...
This setpoint allows the individual winding tempera- 7. Press ENTER () key. A dialog box appears giv- ture sensors to be enabled or disabled. A sensor can ing the range of values. be disabled if it is defective or for service reasons. JOHNSON CONTROLS...
Page 274
Motor Bearings 6. Press ENTER () key. A dialog box appears with High Vibration shutdown and High Vibration Warning the range of allowed values. data boxes on this MOTOR SETPOINTS Screen. The JOHNSON CONTROLS...
Page 275
ADMIN access level and Mo- value. tor Vibration Protection setpoint on the MOTOR DE- 8. Press ENTER () key. TAILS Screen is not set to disabled. To enter desired values: 9. Press CANCEL (X) key to exit. JOHNSON CONTROLS...
Page 276
FORM 160.54-M1 SECTION 32 - SYSTEM CALIBRATION, SERVICE SETPOINTS AND RESET PROCEDURES THIS PAGE INTENTIONALY LEFT BLANK JOHNSON CONTROLS...
1. Shown in Figure 90 on Page 231 through Figure Digital I/O states to be monitored. These screens 99 on Page 279. These screens are used during are preceded by a general screen that provides the the diagnostics and troubleshooting process. They installed software versions. JOHNSON CONTROLS...
Modbus UI - Motor Monitoring – Software in Mo- tor Monitoring Board (only displayed with Microboard Kernel – software that is part of flash memory. software version C.OPT.01.22.307 and later). GUI – Software that is part of the flash memory. JOHNSON CONTROLS...
Main Screen The ADVANCED SECURITY key is used during the - Monitor Monitoring Board (software version manufacturing process and has no field service use. C.OPT.01.22.307 and later) - I/O Board (software version C.OPT.01.21.307 and later) - Keypad test JOHNSON CONTROLS...
TB3-4 Motor Bearing Opposite Shaft End Vibration (accelerometer) TB1-8 Motor Winding Phase C Temperature (50K Ohm thermistor) TB3-6 Not used TB2-11 Not used TB3-8 Not used TB2-8 Not used TB2-5 Not used TB2-2 Not used TB1-11 Not used JOHNSON CONTROLS...
Page 281
TB7-2 Not used 7. Use ◄ and ► keys to select desired value. TB8-5,6 Motor Cooling Coil 8. Press ENTER () key. Leak Detector (float switch) 9. Press CANCEL (X) key to exit. TB8-2,3 Not used JOHNSON CONTROLS...
The voltage value and the current value are directly 4. Using the keypad keys, enter the desired voltage scaled over their respective ranges of 0 to 10VDC and value. 0 to 20mA. For example, when the voltage output (ter- JOHNSON CONTROLS...
Page 283
I/O Board opens this circuit. When Diagnos- tic Mode is exited (DIP Switch 3 is set back to the OFF • Timeout Faults position), outputs revert to Program control. Press the RESET ERROR COUNTERS key to reset these counters to zero. JOHNSON CONTROLS...
If the keypad and ribbon ca- b. Identify row/column coordinate of the key to ble check OK per the above procedures, the mi- be tested. Refer to Figure 42 on Page 99. croboard is most likely the cause of the problem. JOHNSON CONTROLS...
Re- dark blue, light blue and yellow, outlined by a red fer to description of “All Red” test above. border are displayed. If the vertical bars are not stable or straight, or the red border is not com- JOHNSON CONTROLS...
Page 286
• All Black - This test verifies the display’s ability to turn off all pixels to display a completely black screen. Any pixel that does not turn off will ap- pear as a red, green, blue or white dot. Refer to description “All Red” test above. JOHNSON CONTROLS...
1. Display Ribbon Cable should be greater than 3.0VDC. If not, the microboard is defective. Using an Ohmmeter, perform a continuity test on all conductors in the ribbon cable. An open circuit would indicate the ribbon cable is defective. JOHNSON CONTROLS...
Page 288
With the “All Black” test selected, the volt- age at Microboard J5-6 through J5-11, J5-13 through J5-18 and J5-20 through J5-25 should be greater than 1.0VDC. If not, the microboard is defective. JOHNSON CONTROLS...
Failure to install the loop-back connection From or configure the microboard Program Jumper as COM 4b J2-7 (GTX) J2-6 (GRX) noted will result in a FAIL outcome for the test. Microboard Program Jumper JP27 must be installed in position 2 and 3. JOHNSON CONTROLS...
DIAGNOSTICS key to return to the MAIN DIAGNOSTICS Screen. TRANSMIT COMMON RECEIVE +5VDC LOOP-AROUND DIAGNOSTIC CONNECTOR YORK PIN 025-33778-000 INSTALL TO PERFORM DIAGNOSTIC +5VDC LOOP-AROUND TEST LD04250 FIGURE 106 - MICROBOARD - COM 5 SERIAL DATA PORT JOHNSON CONTROLS...
1. The Digital inputs are listed on this screen accord- 6. If a Program Switch (DIP) is in the ON position, the ing to: applicable LED should be illuminated. If the LED is not illuminated, the microboard is defective. JOHNSON CONTROLS...
Page 292
If it is not extinguished, replace the mi- is selected, it will turn off, de-energizing the de- croboard. vice it is connected to. If relay does not de-ener- gize or triac does not turn off, perform appropriate troubleshooting procedure below. JOHNSON CONTROLS...
Page 293
10VAC. If not closed, replace the I/O Board. the Triac is turned off, the voltage will be greater than 100VAC (Slide Valve Actuator) or greater than 20VAC (PRV, Hot gas or Refrigerant Level Control Actuator). JOHNSON CONTROLS...
13 - Proximity probe DC Voltage Reference 16 - REFRIGERANT LEVEL CONTROL, SECTION 19 (Not applicable to P compressors and style "F" - PRESSURE TRANSDUCERS, AND SECTION 20 - and later chillers with “G, Q” and “H5-8” com- TEMPERATURE THERMISTORS. pressors) JOHNSON CONTROLS...
Page 295
All inputs except chan- with the value displayed on the ANALOG IN- nel 0, 15 through 22, 27 and 28 are sensors that PUTS Screen for that value. connect directly to the microboard via shielded JOHNSON CONTROLS...
Page 296
An open circuit would indicate the cable is defective. 3. If steps are OK, problem most likely is in the re- mote device that supplies the remote signal. JOHNSON CONTROLS...
____ Brine Low Evaporator Pressure Cutout ____ Head Pressure Control – P Threshold* (160.54-M1) ____ Smart Freeze Protection ON/OFF ____ Head Pressure Control – I (160.54-M1) ____ Head Pressure Control - D ____ Refrigerant Temp Sensor Enable/Disable (160.54-M1) JOHNSON CONTROLS...
Page 298
(Software ver- sion C.MLM.01.07.xxx (and later) or ture C.OPT.01.14.xxx (and later)) ____ Enable/Disable Extended Run feature ____ Ramp-up Time (Software ver- ____ Count Window sion C.MLM.01.07.xxx (and later) or ____ Count Limit C.OPT.01.14.xxx (and later)) ____ Surge Sensitivity JOHNSON CONTROLS...
Page 299
VSD DETAILS Screen (VSD) Verify the following setpoints were programmed: ____ Set chiller Full Load Amps (FLA) value by adjusting potentiometer on VSD logic board ____ Full Load Amps* (R34 on logic board 031-02506; R28 on all others) ____ Start Current* JOHNSON CONTROLS...
Page 300
____ Motor Cooling Coil Leak Protection ____ Motor Drive Type ____ Manual Baseline or Auto Baseline ____ Anti-Recycle MOTOR SETPOINTS SCREEN (Software version ____ Power Failure Restart C.OPT.01.22.307 and later) ____ Coastdown ____ Temperature Disable ____ Pre-run ____ Winding Setup JOHNSON CONTROLS...
Page 301
____ Quick Start Pulldown Setpoint Offset ____ Report type; Status, Setpoints, Schedule or ____ Pulldown Override Time Sales Order ____ VSD Start Frequency SALES ORDER Screen ____ Mapping Enable ____ Enter system commissioning date ____ Quick Ramp Current Threshold JOHNSON CONTROLS...
Page 302
____ Enter local phone number (Flash memory card version C.MLM.01.05.xxx and later) ____ Enter Chiller Style/Compressor (Flash memory card version C.MLM.01.07.xxx and later) ____ Enter Flow Sensor type (Flash memory card version C.MLM.01.08.xxx and later). JOHNSON CONTROLS...
If stop is selected, data collection will begin when manually initiated, and will stop when all triggers have been sat- isfied and any selected trigger delay has elapsed. JOHNSON CONTROLS...
Page 304
In previous flash memory card versions, the oil pump VSD starts at 25Hz when turned on during System Pre- lube. In this version, the VSD starts at 45Hz, which provides greater reliability in achieving the required 45 PSID target oil pressure at chiller start. JOHNSON CONTROLS...
• Access Level and User ID used to make the change mediately enter a normal coastdown period: • Old Value • Leaving Chilled Liquid – Low Temperature • New Value • Remote Stop • Multi-unit Cycling – Contacts Open JOHNSON CONTROLS...
Page 306
• The message WARNING – REFRIGERANT The hot gas valve position is now animated on the Hot LEVEL OUT OF RANGE and the associated gas bypass screen. lower signal that opens the valve until the level is within range was eliminated. JOHNSON CONTROLS...
Variables include the following: • High Speed Thrust Bearing proximity sensing – Proximity probe or Limit Switch • Flow Sensor – Paddle type (115VAC Digital Input) or factory mounted thermal type sensor (+5VDC Analog Input) JOHNSON CONTROLS...
Page 308
(pin 4) is connected to a Microboard Analog Evaporator: Input. From Sensor pin 2 Microboard J7-1 (+5VDC) pin 4 J7-14 (input to Microboard ) Condenser: From Sensor pin 2 Microboard J7-15 (+5VDC) pin 4 J7-16 (input to Microboard) JOHNSON CONTROLS...
Page 309
Setting the valve preset time to 0 seconds disables this pre-positioning feature. Set- ting the valve preset time to a value greater than 50 seconds has no effect on the pre-lube time. JOHNSON CONTROLS...
If digital is selected, the VSD – LOW PHASE B INVERTER BASEPLATE program reads the paddle-type sensor inputs at the I/O TEMPERATURE board digital inputs TB4-12 (evaporator) and TB4-11 Same as Phase A above. (condenser) and ignores the analog inputs. JOHNSON CONTROLS...
Page 311
Same as Phase A above. SECURITY LOG Screen VSD – HIGH PHASE C INVERTER In previous flash card versions, some setpoint changes BASEPLATE TEMPERATURE were not logged in metric mode. All setpoint changes Same as Phase A above. are now logged. JOHNSON CONTROLS...
Also, if the endpoints are not established within 10 minutes, PRV CALIBRATION UN- • The hot gas valve position must be at 100% AND SUCCESSFUL is displayed. the VSD output frequency must be at maximum before the above surge features are performed. JOHNSON CONTROLS...
Page 314
This compressor motor VSD setpoint default is now 7000 (was 4500). E-LINK GATEWAY INDUCED REBOOTS With previous flash memory card versions, E-Link Gate- way communications could cause the microboard to ran- domly reboot was corrected in this version. JOHNSON CONTROLS...
COMPRESSOR screen. A dialog box displays A, B or C as appropriate) ENTER PASSWORD TO CLEAR FAULT. Diagnostics Screen 5. Enter 1 3 9 7 and press the key (). The communications error counters now count up to 65535 (was 255). JOHNSON CONTROLS...
Page 316
MOTOR – HIGH CURRENT LIMIT was corrected in this version. History Data Storage The data capture has been modified to assure that all data is that which is valid at the instant of the event. JOHNSON CONTROLS...
20 minutes), the VGD is driven to the full open po- sition and WARNING – CONDITIONS OVERRIDE VGD is displayed until the stall detector voltage re- turns to less than two times the high limit setpoint and the warning is manually cleared. JOHNSON CONTROLS...
Page 318
15% FLA motor cur- rent is detected while the chiller is shutdown. Previ- ously, it was not put into effect until the invalid motor current was present for at least 10 seconds. JOHNSON CONTROLS...
02430-000 or 031-02430-001). However, this ver- shutdown is performed. sion (or later versions) is required for microboard • VSD-LOW DC BUS VOLTAGE (P/N 031-02430-001). If the DC Link Voltage falls below 600VDC while running, this shutdown is performed. JOHNSON CONTROLS...
The version and part number for both NEMA 1-4 and CE chillers is C.OPT.01.15A.307 (031-02474-001). LANGUAGES Version C.OPT.01.15.011 was released as English only. This version allows display in English, Chinese Traditional, Chinese Simplified, French, Spanish, Ital- ian, German or Hungarian. JOHNSON CONTROLS...
In this version, LOAD CONTROL MODE is displayed the chiller is running or failed to close during the pre- instead of MOTOR – HIGH CURRENT LIMIT under lube period. The chiller will automatically restart when this condition. the flow switch closes. JOHNSON CONTROLS...
Page 322
Therefore, when the automatic lubri- shutdowns. Report contains only motor run state, PRV cation hardware is present, the auto lube setpoint must position and MV VSD fault code. be enabled. With this setting, no lubrication warnings or shutdown will occur. JOHNSON CONTROLS...
Page 323
This screen displays the fol- NEW SETPOINTS lowing Modbus communications error counters: The following new setpoints are programmed on the Panel to VSD SETUP Screen. VSD to Panel FTR to VSD (if IEE 519 filter present and enabled) JOHNSON CONTROLS...
R-22 and the oil pump package (SETUP Screen) is Current Limit setpoint inputs. This stabilizes these re- set to VARIABLE SPEED, the OIL-VARIABLE SPEED mote setpoint values under noisy conditions and when PUMP-SETPOINT NOT ACHIEVED safety shutdown the inputs are unstable. is not performed. JOHNSON CONTROLS...
Page 325
SI0186 - SOFTWARE ENHANCEMENTS EFFECTIVE OCTOBER 2006 (CONT'D) REMOTE RESET TEMPERATURE RANGE SETPOINT In previous software versions, this setpoint could be set to 10°F or 20°F. In this version it can be set to 10°F, 20°F, 30°F, or 40°F. JOHNSON CONTROLS...
Motor Communications Protocol setpoint must be set to Modbus in this configuration. This configuration is referred to below as “Modbus Protocol configuration”. All MV VSD applications use Modbus protocol. Due to service parts replacement, early production chillers could be in the Modbus configuration. JOHNSON CONTROLS...
Page 327
ACC function in ACC Board and it increments when any surge is the microboard, while the drive is running at less detected by the ACC Board, whether running at than maximum frequency. maximum or less than maximum frequency. JOHNSON CONTROLS...
Page 328
OptiView™ Control Panel – Operation (Form 160.54- selected while a print is in process. The PAGE UP and O1) FIGURE 18 shows this screen in Modbus protocol PAGE DOWN keys are used to scroll to the previous configuration. or next listing. JOHNSON CONTROLS...
Page 329
ACC function increases the VSD or MV VSD Modbus protocol configuration) or MV VSD, these are output frequency, the frequency increase is limited by the surges that are detected while the drive is running the motor current as follows: at maximum frequency. JOHNSON CONTROLS...
Page 330
• Warning – High Pressure Limit – Maximum al- lowable value is 193.0 PSIG, with no change to the default value. • Condenser – High Pressure – Trip/Reset thresh- old is 200/140 PSIG. JOHNSON CONTROLS...
186 A 1750 392 A 274 A 217 A 2000 438 A 312 A 248 A 2250 494 A 345 A 274 A 2500 561 A 391 A 310 A Max. Job/Rated 100% FLA (A) (Programmed Drive Current) JOHNSON CONTROLS...
Page 332
Toll Free Phone Number The label for the toll free number was changed from YORK International North American Toll Free Num- ber to Johnson Controls North America Parts Center. Japanese Language Japanese was added to the selection of languages. Variable Speed Drive Low Frequency Fault In previous software versions, the VSD –...
PRV potentiometer, the software reads the potentiometer input at microboard input J7-10. In previous software versions, the initial ramp is com- plete when either of the following conditions occur: JOHNSON CONTROLS...
Page 334
P, Q FREQUENCY COMMAND MOTOR and H9 compressor chillers, while the chiller is running. INCREASE CURRENT More than 90 %FLA 1.5Hz More than 75 %FLA More than 60 %FLA Less than or equal to 60 %FLA JOHNSON CONTROLS...
Page 335
This option uses two tube bundles in the condenser. The lower bundle is the standard condenser bundle and is piped to the cooling tower water source. The upper tube bundle is used to recover heat waste heat rejection for use in a closed loop heating circuit. JOHNSON CONTROLS...
Page 336
UPS, which prevents a reboot of both on a pow- er failure and keeps communications between them ac- tive throughout the utility power failure. This provides the fastest possible ability to start or restart after gen- erator or utility power is restored. JOHNSON CONTROLS...
Page 337
QUICK START screen, accessible from the SETPOINTS screen when logged in at SERVICE access level. A complete explanation of this feature is contained in Service Manual (Form 160.54-M1), SECTION 29 - QUICK START. JOHNSON CONTROLS...
OptiView™ Control Panel – Operation (Form 160.54-O1). The motor monitoring feature must be enabled. Once enabled, the MOTOR DETAILS and MOTOR SETPOINTS screens are available, where all informa- tion pertinent to the feature are displayed. JOHNSON CONTROLS...
• The ACC MAPPING ENABLE setpoint pro- • The VGD high limit setpoint default changed grammable range increased from 0.5 to 4.0°F to from 0.8V to 0.6V. 0.5 to 20.0°F. • The VGD low limit setpoint default changed from 0.6V to 0.5V. JOHNSON CONTROLS...
Page 340
Temperature Differential (LCHLT – Setpoint) is now occurs, the contacts remain closed into and throughout displayed on the surge map screen. the pre-lube period and the transducer auto-zeroing is not performed (the values from the last auto-zeroing are used). JOHNSON CONTROLS...
Change the format using the new DATE FOR- MAT setpoint on the USER screen, which can be done at the operator access level. The selectable formats are: • DD MMM YYYY (default) • DD.MM.YYYY, or • YYYY-MM-DD JOHNSON CONTROLS...
“Warning – Condenser was changed to conform to the JCI standard "York – Freeze Threat From Low Pressure”. by Johnson Controls". The new BIOS eprom is P/N 031-02429-002. This warning will automatically reset whenever the chiller is running or the Saturated Condenser 2.
Page 343
Fault. This start inhibit feature has been corrected to function properly. 2. Condenser Screen – Corrected the font sizing Heat Pump Duty The Heat Pump Duty enable on the Setup Screen is selectable in Test Op Access Level and above when the refrigerant is R134a. JOHNSON CONTROLS...
(°C), subtract 32° and multiply by 5/9 or 0.5556. Example: (45.0°F - 32°) x 0.5556 = 27.2°C To convert a temperature range (i.e., a range of 10°F) from Fahrenheit to Celsius, multiply by 5/9 or 0.5556. Example: 10.0°F range x 0.5556 = 5.6°C range JOHNSON CONTROLS...
Need help?
Do you have a question about the YORK OPTIVIEW YK Series and is the answer not in the manual?
Questions and answers