Wiring
2-2-4

Wiring CPU Units with AC Power Supplies

AC power supply
CPU Unit (AC power supply type)
Power Supply and Input Circuits
Wiring the CPU Unit Power Supply
• To prevent voltage drops due to starting currents and inrush
currents in other devices, wire the ZEN power supply circuit
separately from other power circuits.
• When using more than one ZEN, to prevent voltage drops due to
inrush current and circuit-breaker malfunctions, it is
recommended that each one is wired separately.
• To prevent the influence of noise from power lines, twist the
power lines. Wiring via a 1-to-1 isolation transformer is also
effective.
• Use wires that are thick enough to allow for voltage drops and
current variations within the allowable range.
• Include a circuit protector or breaker installed separately from
other circuits in the power supply circuit for the ZEN.
Circuit
protector
Isolation
transformer
CPU Units and Expansion I/O Units with 10 I/O Points
100 to 240 VAC, 50/60 Hz
L
N
Circuit
protector
L
N
NC
CPU Unit with 10 I/O points
Input device
I0
I1
I2
I3
I4
I5
Section 2-2
Input device
L
N
Expansion I/O Unit
(AC input type)
Input device
L
N
IN0 IN1 IN2 IN3
ZEN-8E1AR Expansion I/O Unit
(AC input type)
41