Wiring
2-2-2
Connectable Wires
Note
Note
2-2-3
Wiring Power Supply and Input Lines
Fires may occasionally occur. Tighten the terminal block screws to a
torque of 0.565 to 0.6 N·m (5 to 5.3 in-lb).
Precautions for Correct Use
40
One-line connection 0.2 to 2.5 mm
Two-line connection 0.2 to 0.75 mm
When using a 2-line connection, use wires of the same size for
both lines.
• Strip the sheath back 6.5 mm.
6.5 mm
When using a 2-line connection, use terminals of the same size
for both lines.
• Use a flat-blade screwdriver to tighten the terminal block screws
and tighten the screws to a torque of 0.565 to 0.6 N·m (5 to 5.3
in-lb).
• Recommended screwdriver: SZS0.6X3.5 or SZF1-0.6X3.5
manufactured by Phoenix Contact
• Do not use terminals that are not connected as relay terminals.
2
(Equivalent to AWG24 to AWG14)
2
(Equivalent to AWG24 to AWG19)
CAUTION
Section 2-2