Wiring
Surface Mounting
2-2
Wiring
2-2-1
External Wiring
■
38
A
22.5
80
Unit
CPU Units with 10 I/O Points
CPU Units with 20 I/O Points
Expansion I/O Units
With an Expansion Unit, pull out the DIN Track mounting hooks on
the top and bottom of the Unit to secure the Unit with screws.
Do not run ZEN I/O lines in the same duct or conduit as power lines.
Hanging Ducts
Leave at least 300 mm between the power cables and the I/O or
control wiring, as shown in the following diagram.
35
35
97
A
60
112.5
---
Section 2-2
Screw
Tightening
size
torque
M4
1.03 N·m max.
M3
0.46 N·m max.