Three-phase Phase-sequence Phase-loss Relay
K8AB-PM
Ideal for monitoring 3-phase power supplies
for industrial facilities and equipment.
• Monitor overvoltages, undervoltages, phase sequence, and
phase loss for three-phase 3-wire or 4-wire power supplies with
just one Unit.
Switch setting for 3-phase 3-wire or 3-phase 4-wire power
supply.
• Two SPDT output relays, 6 A at 250 VAC (resistive load).
Output overvoltages and undervoltages using separate relays.
• World-wide power specifications supported by one Unit
(switchable).
• Output status can be monitored using LED indicator.
Model Number Structure
■ Model Number Legend
K8AB-@@
1
2 3
1. Basic Model
K8AB: Measuring and Monitoring Relays
2. Functions
PM:
Three-phase Phase-sequence Phase-loss Relay (Simultaneous upper and lower monitoring)
3. Rated Input Voltage
1:
115, 127, 133, 138, 200, 220, 230, 240 VAC
2:
220, 230, 240, 277, 380, 400, 415, 480 VAC
Single K8AB Monitors 3-phase Power Supply with 3 or 4 Wires
Monitoring Relays can be used to monitor 3-phase power supplies with 3 or 4 wires simply by changing DIP switch settings.
A Single K8AB Can Monitor a 3-phase Power Supply Anywhere in the World
Reduces Maintenance Parts Inventory
K8AB-P@1
K8AB-P@2
Cat. No. N146-E1-02
Phase to phase voltage (3 wires)
L1
L2
L3
400VAC
400VAC
400VAC
SW3
SW4
ON
SW2
OFF
ON
SW2
OFF
Three-phase Phase-sequence Phase-loss Relay
Phase to neutral voltage (4 wires)
L1
L2
L3
230VAC
230VAC
230VAC
ON
ON
P-N
138 V
P-P
240 V
P-N
277 V
P-P
480 V
N
ON
OFF
OFF
ON
133 V
127 V
230 V
220 V
240 V
230 V
415 V
400 V
K8AB-PM
OFF
OFF
115 V
200 V
220 V
380 V
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the K8AB-PM Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Omron K8AB-PM Series

  • Page 1 Three-phase Phase-sequence Phase-loss Relay K8AB-PM Ideal for monitoring 3-phase power supplies for industrial facilities and equipment. • Monitor overvoltages, undervoltages, phase sequence, and phase loss for three-phase 3-wire or 4-wire power supplies with just one Unit. Switch setting for 3-phase 3-wire or 3-phase 4-wire power supply.
  • Page 2: Ordering Information

    Ordering Information ■ List of Models Three-phase Phase-sequence Phase-loss Relay Rated input (See note 2.) Model 3-phase 3-wire mode 200, 220, 230, 240 VAC K8AB-PM1 3-phase 4-wire mode 115, 127, 133, 138 VAC 3-phase 3-wire mode 380, 400, 415, 480 VAC K8AB-PM2 3-phase 4-wire mode 220, 230, 240, 277 VAC...
  • Page 3 ■ Specifications Input frequency range 45 to 65 Hz Overload capacity Continuous input: 115% of maximum input, 10 s max.: 125% of maximum input Set value ±10% of full scale Setting error Operating value Operating time Set value ±0.5 s Startup lock time Operating value ±2% Repeat error...
  • Page 4: Operation Indicators

    Connections ■ Wiring Diagram Overvoltage/Undervoltage and Phase Sequence/Phase Loss Operation Diagram Overvoltage L2 L3 setting value Hysteresis: Fixed at 5% Input Hysteresis: Fixed at 5% Voltage input Undervoltage setting value Flashing Overvoltage alarm indicator Flashing T: Operating time (0.1 to 30 s) Undervoltage alarm indicator Overvoltage relay Undervoltage relay...
  • Page 5: Setting Knobs

    Nomenclature ■ Front Indicators Terminal block (See notes 1 and 2.) Item Meaning Power indicator Lit when power is being supplied (see note). (PWR: Green) Relay status indicator Lit when relay is operating (normally lit). (RY: Yellow) Overvoltage knob Alarm Overvoltage: Lit when there is an overvoltage.
  • Page 6: Dip Switch Settings

    ■ Operation and Setting Methods Connections 1. Input L2 L3 Connect to L1, L2, and L3 (for three-phase three-wire mode) or L1, L2, L3, and N (for three-phase four- wire mode), depending on the mode selected using pin 2 on the DIP switch. The Unit will not operate correctly if the DIP switch setting and the wiring do not agree.
  • Page 7: Setting Method

    Setting Method 1. Overvoltage The overvoltage knob (OVER) is used to set the overvoltage threshold. The overvoltage can be set to between −30% and 25% of the rated input voltage. Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the same level.) Use this as a guide to set the voltage.
  • Page 8: Safety Precautions

    Safety Precautions ■ Precautions for Safe Use ■ Precautions for Correct Use Make sure to follow the instructions below to ensure safety. For Proper Use 1. Do not use or keep this product in the following environments. • Outdoors, or places subject to direct sunlight or wearing 1.
  • Page 9: Questions And Answers

    Questions and Answers Checking Operation How to Measure the Operating Time Overvoltages Overvoltage Gradually increase the input from 80% of the setting. Change the input suddenly from 0% to 120% of the set The input value will equal the operating value when the value and measure the time until the Unit operates.
  • Page 10 Questions and Answers Overvoltage Detection When Only One Phase Exceeds Load-side Phase Loss the Overvoltage Threshold The K8AB-PM@ monitors each of the three-phase voltages. In principle, phase loss cannot be detected on the load side This means an overvoltage is detected if even only one because the K8AB-PM@ measures three-phase voltage to phase exceeds the threshold value.
  • Page 11 K8AB-PM Cat. No. N146-E1-02 Three-phase Phase-sequence Phase-loss Relay...
  • Page 12: Warranty And Application Considerations

    Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS.

This manual is also suitable for:

K8ab-pm2K8ab-pm1

Table of Contents