Omron K3HB - MANUAL 2 Manual page 67

Digital indicators
Hide thumbs Also See for K3HB - MANUAL 2:
Table of Contents

Advertisement

List of Settings
Communications Setting Level
Variable
Address
Parameter
type
name
CA
0000
Communications
unit number
0001
Baud rate
0002
Communications
data length
0003
Communications
stop bits
0004
Communications
parity
0005
Send wait time
Note
The values beginning with H' in the Monitor/Setting range column are used when setting or monitor-
ing data via communications.
Advanced Function Setting Level
Variable
Address
Parameter
type
name
CB
0002
Output OFF delay
0003
Shot output
0004
Output logic
0009
Bank selection
Note
(1) The values beginning with H' in the Monitor/Setting range column are used when setting or moni-
toring data via communications.
(2) If the event connector is provided as a standard feature or an event connector is added, use EV
for the "bank selection" setting.
2-22
Charac-
Monitor/Setting range
ter
u-no
H'00000000 to H'00000063: (0 to 99)
bps
H'00000000: 9.6 (0), H'00000001: 19.2 (1),
H'00000002: 38.4 (2)
len
H'00000000: 7 (0), H'00000001: 8 (1)
sbit
H'00000000: 1 (0), H'00000001: 2 (1)
prty
H'00000000: None (0), H'00000001: Even (1),
H'00000002: Odd (2)
sdwt
H'00000000 to H'00000063: (0 to 99)
Charac-
Monitor/Setting range
ter
off-d
H'00000000 to H'000007CF: (0 to 1999)
shot
H'00000000 to H'000007CF: (0 to 1999)
out-n
H'00000000: Close in alarm (0),
H'00000001: Open in alarm (1)
bnk-c
H'00000000: OFF (0), H'00000001: KEY (1),
H'00000002: EV (2)
Character
Default
Decimal point
setting
0 to 99
1
---
9. 6, 19. 2. 38. 4
9. 6
---
7, 8
7
---
1, 2
2
---
none, even, odd
even
---
0 to 99
20
---
Character
Default
Decimal point
setting
0 to 1999
0
---
0 to 1999
0
---
n-o, n-c
n-o
---
off, key, ev
off (See
---
note 2.)
Section 2
Unit
---
kbps
bit
bit
---
ms
Unit
ms
ms
---
---