Commands and Responses (CompoWay/F Communications)

1-9-15 Move to Setting Area 1

Command
Response

1-9-16 Move to Protect Level

Command
Response

1-9-17 Initialize Settings

Command
1-20
Command
Related
MRC
SRC
code
information
"30"
"05"
"07"
"00"
Use this command to move to setting area 1.
The command is used in setting area 0. Nothing happens if the command is
used in setting area 1.
If the command is used when "Initial setting protect" is set to 2 (Disable move
to input initial setting level), an operation error will result.
To use this command, "Write via communications" must be enabled using the
"Write via communications" operation command.
MRC
SRC
Response code
"30"
"05"
"0000"
Response codes: The above indicates a normal end. For the response codes,
see 1-7 Operation Commands (CompoWay/F Communications) (page 1-11).
Command
Related
code
information
MRC
SRC
"30"
"05"
"08"
"00"
Use this command to move to protect level.
This command is used in setting area 0. If used in setting area 1, an operation
error will result.
To use this command, "Write via communications" must be enabled using the
"Write via communications" operation command.
MRC
SRC
Response code
"30"
"05"
"0000"
Response codes: The above indicates a normal end. For the response codes,
see 1-7 Operation Commands (CompoWay/F Communications) (page 1-11).
Command
Related
MRC
SRC
code
information
"30"
"05"
"0B"
"00"
This returns all settings to the initial settings.
This command is used in setting area 1. If used in setting area 0, an operation
error will result.
To use this command, "Write via communications" must be enabled using the
"Write via communications" operation command.
Section 1-9