FINS-mini Text
Response text
FINS-mini response text consists of the MRC and SRC, followed by an MRES
(main response code) and SRES (sub response code), and then the required
data.
Node
Sub-
No.
address
STX
End code
Response text
02H
"00"
MRC
SRC
MRES
SRES
2
2
2
2 bytes
If the specified FINS-mini command was not successfully executed, the
response will only contain the MRC, SRC, MRES and SRES.
List of FINS-mini Service Commands (CompoWay/F Communications)
MRC
SRC
Service name
"01"
"01"
Monitor value/setting data read
"01"
"02"
Monitor value/setting data write
"01"
"04"
Monitor value/setting data com-
pound read
"01"
"13"
Monitor value/setting data com-
pound write
"01"
"10"
Monitor value/setting data com-
pound stored read
"01"
"11"
Monitor value/setting data com-
pound read store (write)
"01"
"12"
Monitor value/setting data com-
pound read store check (read)
"05"
"03"
Machine attribute read
"06"
"01"
Controller status read
"08"
"01"
Echo-back test
"30"
"05"
Operation command
FINS-mini
ETX BCC
03H
Data
Reads monitor values/setting
data.
Writes monitor values/setting
data.
Performs multiple reads of moni-
tor values/setting data.
Performs multiple writes of mon-
itor values/setting data.
Sequentially reads contents of
addresses specified in "monitor
value/setting data compound
read store."
Specifies addresses to be read
using "monitor value/setting data
compound stored read."
Reads the contents stored using
"variable area compound read
store."
Reads the model and other
attributes.
Reads the operation status.
Performs an echo-back test.
Commands such as Run/Stop,
AT Execute/Cancel, and "Move
to setting area 1".
Section 1-3