List of Settings
Linear Output Level
Variable
Address
Parameter
type
name
C9
0000
Linear current
type
0001
Linear voltage
type
0002
Linear output
upper limit
0003
Linear output
lower limit
Note
The values beginning with H' in the Monitor/Setting range column are used when setting or monitor-
ing data via communications.
Communications Setting Level
Variable
Address
Parameter
type
name
CA
0000
Communications
unit number
0001
Baud rate
0002
Communications
data length
0003
Communications
stop bits
0004
Communications
parity
0005
Send wait time
Note
The values beginning with H' in the Monitor/Setting range column are used when setting or monitor-
ing data via communications.
Advanced Function Setting Level
Variable
Address
Parameter
type
name
CB
0000
PASS output
change
0001
Hysteresis
0002
Output OFF delay
0003
Shot output
0004
Output logic
0005
Output refresh
stop
0009
Bank selection
000A
Startup
compensation
timer
000C
Standby
sequence
Note
(1) If the event connector is provided as a standard feature or an event connector is added, use EV
for the "bank selection" set.
(2) The values beginning with H' in the Monitor/Setting range column are used when setting or moni-
toring data via communications.
2-16
Charac-
Monitor/Setting range
ter
lset. c
H'00000000: 0-20 mA (0), H'00000001: 4-20 mA (1) 0-20, 4-20
lset. v
H'00000000: 0-5 V (0), H'00000001: 1-5 V (1),
H'00000002: 0-10 V (2)
H'FFFFB1E1 to H'0001869F: −19999 to 99999
lset. h
(Time limit is OFF. Lower limit of P is 0.)
H'00000000 to H'0001869F: 0 to 99999
(Time unit is min.)
H'00000000 to H'000176D7: 0.00.00 to 9.59.59
(Time unit is hr:min:s.)
H'00000000 to H'0001850F: 00.00.0 to 99.59.9
(Time unit is min:s:ms.)
lset. l
Same as above
Charac-
Monitor/Setting range
ter
u-no
H'00000000 to H'00000063: (0 to 99)
bps
H'00000000: 9.6 (0), H'00000001: 19.2 (1),
H'00000002: 38.4 (2)
len
H'00000000: 7 (0), H'00000001: 8 (1)
sbit
H'00000000: 1 (0), H'00000001: 2 (1)
prty
H'00000000: None (0), H'00000001: Even (1),
H'00000002: Odd (2)
sdwt
H'00000000 to H'00000063: (0 to 99)
Charac-
Monitor/Setting range
ter
pass
H'00000000: LL (0), H'00000001: L (1),
H'00000002: PASS (2), H'00000003: H (3),
H'00000004: HH (4)
hys
H'00000000 to H'0000270F: 0 to 9999 (Time limit is
OFF. Lower limit of P is 0.)
H'00000000 to H'00001747: 0.00.00 to 0.59.59
(Time unit is hr:min:s.)
H'00000000 to H'0000257F: 00.00.0 to 09.59.9
(Time unit is min:s:ms.)
off-d
H'00000000 to H'000007CF: (0 to 1999)
shot
H'00000000 to H'000007CF: (0 to 1999)
out-n
H'00000000: Close in alarm (0),
H'00000001: Open in alarm (1)
o-stp
H'00000000: OFF (0), H'00000001: OUT (1),
H'00000002: ALL (2)
bnk-c
H'00000000: OFF (0), H'00000001: KEY (1),
H'00000002: EV (2)
s-tmr
H'00000000 to H'0000270F: (0.0 to 99.9)
stdby
H'00000000: OFF (0), H'00000001: ON (1)
Character
Default
Decimal point
setting
4-20
---
0-5, 1-5, 0-10
1-5
---
:9999 to 99999
99999
According to the
0. 00. 00 to 99999
decimal position
0. 00. 00 to
setting. The time
9. 59. 59
unit, however, is
0. 00. 00 to
indicated as
99. 59. 9
*.**.** for
hr:min:s and as
**.**.* for
min:s:ms.
Same as above
R: :9999
Same as above
P: 0
Character
Default
Decimal point
setting
0 to 99
1
---
9. 6, 19. 2. 38. 4
9. 6
---
7, 8
7
---
1, 2
2
---
none, even, odd
even
---
0 to 99
20
---
Character
Default
Decimal point
setting
ll, l, pass, h,
pass
---
hh
0 to 9999
1
According to the
0. 00. 00 to
decimal position
0. 59. 59
setting. The time
00. 00. 0 to
unit, however, is
09. 59. 9
indicated as
*.**.** for
hr:min:s and as
**.**.* for
min:s:ms.
0 to 1999
0
---
0 to 1999
0
---
n-o, n-c
n-o
---
off, out, all
off
---
off, key, ev
off (See
---
note 1.)
0. 0 to 99. 9
0. 0
1
off, on
off
---
Section 2
Unit
---
---
---
---
Unit
---
kbps
bit
bit
---
ms
Unit
---
---
R:
100 ms
P: ms
R:
100 ms
P: ms
---
---
---
s
---

Advertisement