Alarms, Volvo Penta; Alarm, Volvo Penta - THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Manual

Genset controller option j – canbus j1939
Hide thumbs Also See for MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939:
Table of Contents

Advertisement

MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
Alarm, status and measurement table (read only) function code 04h.
Addr.
Content
1020
EIC alarms, MEC 310
controller
1024
EIC alarms (DM 1)
PM077 R1 09/08/20

Alarms, Volvo Penta

Type
Bit 0
7570 EIC communication error
Bit 1
7580 EIC warning
Bit 2
7590 EIC shutdown
Bit 3
7600 EIC overspeed
Bit 4
7610 EIC coolant water temperature 1
Bit 5
7620 EIC coolant water temperature 2
Bit 6
7630 EIC oil pressure 1
Bit 7
7640 EIC oil pressure 2
Bit 0
EIC overspeed, warning
Bit 1
EIC oil pressure, warning
Bit 2
EIC oil temperature, warning
Bit 3
EIC high coolant temperature, warning
Bit 4
EIC low coolant level, warning
Bit 5
EIC fuel pressure, warning
Bit 6
EIC ECM yellow lamp, warning
Bit 7
EIC ECM red lamp, shutdown
Bit 8
EIC high inlet air temperature, warning
Bit 10 EIC battery voltage, warning
Bit 11 EIC low oil level, warning