Display Functions - THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Manual

Genset controller option j – canbus j1939
Hide thumbs Also See for MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939:
Table of Contents

Advertisement

MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
The display indicates both readings and alarms. Illustrated below are examples with icons and
English language.
MEC 310
version
Battery
RPM
00000.h
1
0 d
2
0 d
27/11 2006
00000.h
Alarm list
High Battery
Ack
Parameter
D+ delay
0.0 s
10.0 s
Min. value
Actual value
The available parameters depend on the set options. Some parameters can only
be changed using the TPS 300 programming software. The parameter list will
automatically be abandoned, if no button is pressed during a 30 sec. period.
PM077 R1 09/08/20

Display functions

Type and software version.
24.0 V
0
Battery voltage, RPM and running hours counter.
Service timer 1 and 2.
0 h
0 h
Date and time.
14:30:55
Press
2 alarm(s)
Active alarm list . The alarm list pops up
automatically, when an alarm appears. When the
arrow is present, more alarms are active. Press ▼
to scroll through the list. Exit the list by pressing
ESC.
2 alarm(s)
Press
Parameter example: D+ delay setting. Use ▲ or ▼
to scroll through the settings list. If change of
settings is necessary, press
password. Then use ▲ or ▼ to change values.
Use ESC to leave settings.
100.0 s
Max. value
Page 14
to enter the list of active alarms.
to enter the parameter setting.
and enter the