John Deere Jdec (J1939) - THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Manual

Genset controller option j – canbus j1939
Hide thumbs Also See for MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939:
Table of Contents

Advertisement

MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
Warnings and shutdowns
Warning/shutdown list
Low oil pressure
Intake manifold
Coolant temperature
Fuel injection pump
Fuel temperature
ECU failure
EIC yellow lamp
EIC red lamp
FMI indication ' – ' means that the alarm in question is not supported.
Write commands to engine controller
Engine controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are enabled in
setting 7563 (EIC Controls).
Engine speed
CANbus ID for speed control: 0x0c000000. J1939 TSC1.
The speed regulation is enabled in setting 2781 (Reg. output) and 7563 (EIC
Controls).
PM077 R1 09/08/20

John Deere JDEC (J1939)

J1939 codes
SPN
100
105
110
1076
174
2000
-
-
Page 22
FMI
FMI
warning
shutdown
18
1
16
-
16
0
10
6
-
16
-
6
X
-
-
X
THOMSON TECHNOLOGY

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mec 310

Table of Contents