MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
Addr.
Content
Alarms, MTU MDEC series – 2000/4000 – module 302 & 303
Alarm, status and measurement table (read only) function code 04h.
Addr.
Content
1020
EIC alarms, MEC 310
controller
1024
EIC alarms, engine
controller
PM077 R1 09/08/20
Type
Bit 15
EIC
Power supply high voltage
Type
Bit 0
EIC communication error
Bit 2
EIC shutdown
Bit 3
EIC overspeed
Bit 4
EIC coolant water temperature 1
Bit 5
EIC coolant water temperature 2
Bit 6
EIC oil pressure 1
Bit 7
EIC oil pressure 2
Bit 0
EIC overspeed, shutdown
Bit 1
EIC low oil pressure, warning
Bit 2
EIC low oil pressure, shutdown
Bit 3
EIC low coolant level, shutdown
Bit 4
EIC MDEC ECU failure, shutdown
Bit 5
EIC high coolant temperature, warning
Bit 6
EIC high coolant temperature, shutdown
Bit 7
EIC high intercooler coolant temp, warning
Bit 8
EIC high oil temperature, shutdown
Bit 9
EIC high charge air temperature, shutdown
Bit 10 EIC defect coolant level switch, warning
Bit 11 EIC MDEC yellow alarm, warning
Bit 12 EIC MDEC red alarm, shutdown