During a start sequence the start relay is deactivated, if:
-
the speed exceeds the RPM running setting
-
the running feedback input is ON, or
-
the measured frequency of the generator is above 30Hz, or
-
the speed information given by the EIC communication is above the limit
EICoverspeed_6010
During a stop sequence the generator is considered to be stopped, if:
-
the speed is below the running setting
-
the running feedback input is OFF, or
-
the measured frequency of the generator is below 30Hz, or
-
the speed information given by the EIC communication is below the limit
EICoverspeed_6010
PM077 R1 09/08/20

Running detection

Page 15