Caterpillar/Perkins (J1939); Erkins (J1939) - THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Manual

Genset controller option j – canbus j1939
Hide thumbs Also See for MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939:
Table of Contents

Advertisement

MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
The J1939 warnings/shutdowns with corresponding SPN and FMI numbers in
this chapter refer to those that will automatically appear in the alarm list. The
alarms can be acknowledged from the display.
The available alarms vary from engine type to engine type. Besides these, the
entire log list can be read in the engine controller by holding the 'LOG' button
for 3 seconds.
Warnings and shutdowns
Warning/shutdown list
Low oil pressure
Intake manifold #1 P
Coolant temperature
High inlet air temp.
Fuel temperature
Overspeed
EIC yellow lamp
EIC red lamp
FMI indication ' – ' means that the alarm in question is not supported.
Write commands to engine controller
Engine controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are enabled in
setting 7563 (EIC Controls).
Engine speed
CANbus ID for speed control: 0x0c000000. J1939 TSC1.
The speed regulation is enabled in setting 2781 (Reg. output) and 7563 (EIC
Controls).
PM077 R1 09/08/20

Caterpillar/Perkins (J1939)

J1939 codes
SPN
100
102
110
172
174
190
-
-
Page 16
FMI
FMI
warning
shutdown
17
1
15
-
15
1
15
-
15
-
15
0
X
-
-
X
THOMSON TECHNOLOGY

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mec 310

Table of Contents