MEC 310 GENSET CONTROLLER - Option J – CANbus J1939
Warnings and shutdowns
Warning/shutdown list
Low oil pressure
Intake manifold #1 P
Coolant temperature
High inlet air temp.
Fuel temperature
Overspeed
EIC yellow lamp
EIC red lamp
FMI indication ' – ' means that the alarm in question is not supported.
Write commands to engine controller
Engine controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are enabled in
setting 7563 (EIC Controls).
Engine speed
CANbus ID for speed control: 0xc000003.
For J1939 TSC1, the source address of the ML-2 controller is 3.
For the Iveco Vector 8 type only: CANbus ID for speed control: 0xcFF0027.
The speed regulation is enabled in setting 2781 (Reg. output) and 7563 (EIC
Controls).
PM077 R1 09/08/20

Iveco (J1939)

J1939 codes
FMI
SPN
warning
100
17
102
15
110
15
172
15
174
15
190
15
-
X
-
-
Page 21
FMI
shutdown
1
-
0
-
-
0
-
X