Alarm, status and measurement table (read only) function code 04h.
Addr.
Content
1020
EIC alarms, MEC 310
controller
PM077 R1 09/08/20
Alarms, General J1939
Type
Bit 0
7570 EIC communication error
Bit 1
7580 EIC warning
Bit 2
7590 EIC shutdown
Bit 3
7600 EIC overspeed
Bit 4
7610 EIC coolant water temperature 1
Bit 5
7620 EIC coolant water temperature 2
Bit 6
7630 EIC oil pressure 1
Bit 7
7640 EIC oil pressure 2
Page 37