17.3.4 To prevent the outdoor unit from falling over

Installer and user reference guide
86
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface,
raise the unit to provide a free space of more than 150 mm under the outdoor unit.
Drain holes (dimensions in mm)
Model
RXYSA8
RXYSA10 +
RXYSA12
a Drain holes
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4 Attach the ends of the cables.
5 Tighten the cables.
Bottom view [mm]
a
498
68
66
72
49
90
54
307
858
872
892
916
a
20
216
130
98
21
89
32
VRV 5-S system air conditioner
RXYSA8~12AMY1B
4P752782-1A – 2024.02