20.4 To connect the cool/heat selector switch option

RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
NOTICE
Do NOT use the outputs as a power source. Instead, use each output to energize a
relay that controls the external circuit.
WHT
BLK GRY PPL
X2M
SVEO
SVS
a
b
a SVEO output terminals (1 and 2)
b SVS output terminals (1 and 2)
c Cable to SVS output device (example)
Example:
X2M
1
2
(SVS)
a
a SVS output terminal
b Relay
c AC power supply 220~240 V AC
d External alarm
INFORMATION
Sound data about the refrigerant leakage alarm are available in the technical data
sheet of the user interface. E.g. the BRC1H52* controller generates an alarm of 65 dB
(sound pressure, measured at 1 m distance from the alarm).
In order to control the cooling or heating operation from a central location, the
following optional cool/heat selector switch (KRC19-26A) can be connected:
1 Connect the cool/heat selector switch to terminal X1M of the cool/heat
selector PCB.
1
X1M
2
3
X1M Terminal on the PCB
KRC19-26A Cool/heat selector switch
2 Route the wires in the switchbox as shown:
c
c
b
A
KRC19-26A
B
C
20
Electrical installation
|
d
Installer and user reference guide
127