Piping installation

18.1.3 Refrigerant piping insulation

18.1.4 To select the piping size

A: Piping between outdoor unit and (first) refrigerant branch kit
Installer and user reference guide
88
Outer diameter (Ø)
6.4 mm (1/4")
9.5 mm (3/8")
12.7 mm (1/2")
15.9 mm (5/8")
19.1 mm (3/4")
22.2 mm (7/8")
25.4 mm (1")
(a)
Depending on the applicable legislation and the maximum working pressure of the unit
(see "PS High" on the unit name plate), larger piping thickness might be required.
Use polyethylene foam as insulation material:
-
with a heat transfer rate between 0.041 and 0.052  W/mK (0.035 and
0.045 kcal/mh°C)
-
with a heat resistance of at least 120°C
Insulation thickness:
Ambient temperature
≤30°C
>30°C
Determine the proper size using the following tables and reference figure (only for
indication).
B'
b
B'''
d
C
C
C
a
a
a
a
10
11
1
a1~a11 VRV DX indoor units
b1~b3 SV units
c First branch kit (header)
d Indoor branch kit (refnet)
e VRV 5-S outdoor unit
A~C Piping
Choose from the following table in accordance with the outdoor unit capacity type.
In case there is no first indoor branch kit (c), pipe A is connected to the first SV unit
or VRV DX indoor unit.
Temper grade
Annealed (O)
Annealed (O)
Half hard (1/2H)
Half hard (1/2H)
Humidity
75% to 80% RH
≥80% RH
e
A
B
b
1
2
B''
d
C
C
C
C
C
a
a
a
a
2
3
4
5
6
(a)
Thickness (t)
≥0.80 mm
≥0.99 mm
≥0.80 mm
≥0.88 mm
Minimum thickness
15 mm
20 mm
B
b
3
B
d
C
C
C
a
a
a
7
8
9
VRV 5-S system air conditioner
4P752782-1A – 2024.02
Ø
t