To close the drain holes and attach the drain socket

6.3.6 To prevent the outdoor unit from falling over

RXM-A, ARXM-A
R32 split series
4P718129-3A – 2023.07
a Drain port
b Bottom frame
c Drain plug
d Hose (field supply)
NOTICE
In cold areas, do NOT use a drain socket, hose and caps (1, 2) with the outdoor unit.
Take adequate measures so that the evacuated condensate CANNOT freeze.
1 Install drain caps 1 and 2 (accessory). Make sure the edges of the drain caps
close off the holes completely.
a
b
a Bottom frame
b Drain cap
2 Install the drain socket.
a
b
c
b
a Drain hole. Install a drain cap (2).
b Drain hole. Install a drain cap (1).
c Drain hole for drain socket
In case the unit is installed in places where strong wind can tilt the unit, take
following measure:
1 Prepare 2 cables as indicated in the following illustration (field supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the
cables from scratching the paint (field supply).
4 Attach the ends of the cables.
5 Tighten the cables.
b
a
c
d
b
a
a
6
Unit installation
|
Installer reference guide
31