To Close The Outdoor Unit; Mounting The Outdoor Unit; To Provide The Installation Structure - Daikin VRV 5-S User Reference Manual

System air conditioner
Table of Contents

Advertisement

17
|
Unit installation

17.2.3 To close the outdoor unit

17.3 Mounting the outdoor unit

17.3.1 To provide the installation structure

Installer and user reference guide
84
8 HP
NOTICE
When closing the outdoor unit cover, make sure that the tightening torque does NOT
exceed 4.1 N•m.
8 HP
Check the strength and level of the installation ground so that the unit will not
cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance with the
foundation drawing.
Prepare four sets of anchor bolts, nuts, and washers (field supply) as follows:
[mm]
10+12 HP
10+12 HP
4× M12
a
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02