17.1.1 Installation site requirements of the outdoor unit
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
INFORMATION
Also read the following requirements:
▪
General installation site requirements. See the "General safety precautions"
chapter.
▪
Service space requirements. See the "Technical data" chapter.
▪
Refrigerant piping requirements (length, height difference). See further in this
"Preparation" chapter.
INFORMATION
Equipment meets the requirement for commercial and light-industrial location when
professionally installed and maintained.
▪
The outdoor unit is designed for outdoor installation only, and for the following
ambient temperatures:
Heating
Cooling
Note: For indoor installation of the outdoor unit, check the applicable legislation.
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies with specifications that are
designed to provide reasonable protection against such interference. However, there
is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
c
b
a d
e
(mm)
a Personal computer or radio
b Fuse
c Earth leakage protector
d User interface
e Indoor unit
f Outdoor unit
▪
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for
power and transmission lines.
▪
Provide sufficient space around the unit for servicing and air circulation.
▪
Make sure the installation site withstands the weight and vibration of the unit.
▪
Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪
Make sure the unit is level.
▪
Select a place where rain can be avoided as much as possible.