Overview: Flowchart; Safety Measures; No Safety Measure - Daikin VRV 5-S User Reference Manual

System air conditioner
Table of Contents

Advertisement

16.3.1 Overview: flowchart

Determine required safety
measure based on 'All other
floors' of the graph and table.

No safety measure

Note: The flowchart is an overview. Always refer to the full text mentioned in this manual for clear understanding and detailed
explanation.

16.4 Safety measures

16.4.1 No safety measure

RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
Procedure to check required
countermeasure for indoor unit
Determine total amount of
refrigerant in the system.
Total charge amount [kg]
Determine the smallest area out of:
- the room where an indoor unit is installed,
- each of the rooms served by a ducted indoor
unit installed in a different room
A
min
NO
Indoor unit installed/
lowest underground floor?
See Step 3 in
above text
Alarm +
Natural ventilation
+
OR
Alarm +
shut-off valve [SV unit]
+
When the room area is sufficiently large, no safety measures are required. This also
includes an indoor unit installed in the lowest underground floor.
Therefore the R32 safety system in the indoor unit in a sufficiently large room can
be deactivated (active by default) by changing the setting in the user interface as
shown below:
Field settings
Setting
1
15/25
16
|
[m²]
YES
conditioning on
Determine required safety
measure based on 'Lowest
underground floor' of the graph
and table.
No safety measure
No safety measure
st
code
Function
13
R32 leak safety
system setting
Special requirements for R32 units
See Step 1 in above text
See Step 2 in above text
Alarm
OR
Natural ventilation
nd
2
code
01
Disabled
Installer and user reference guide
See Step 3 in
above text
NOT allowed
Description
67

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv 5Rxysa8amy1bRxysa10amy1bRxysa12amy1b

Table of Contents