Charging refrigerant

19.6 Error codes when charging refrigerant

19.7 To fix the fluorinated greenhouse gases label

Installer and user reference guide
114
11 Charge refrigerant until the remaining determined additional refrigerant
amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant charge mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the refrigerant.
Operating with the stop valves closed will damage the compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of the refrigerant charging
port. The tightening torque for the lid is 11.5 to 13.9 N•m.
INFORMATION
If a malfunction occurs, the error code is displayed on the outdoor unit's 7‑segments
display and on the user interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the malfunction code
and take corresponding action,
4
codes" [
 159].
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
f
GWP: XXX
2
1
+
1
GWP × kg
1000
a If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total refrigerant charge
expressed as tonnes CO
f GWP = Global Warming Potential
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2 Fix the label on the inside of the outdoor unit. There is a dedicated place for it
on the wiring diagram label.
"25.3  Solving problems based on error
a
kg
b
1
=
kg
c
2
=
d
kg
2
=
=
e
tCO
eq
2
equivalent.
2
equivalent.
2
equivalent tonnes: GWP value of the
2
VRV 5-S system air conditioner
4P752782-1A – 2024.02