20.1.6 Specifications of standard wiring components
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752782-1A – 2024.02
Component
Power supply
MCA
cable
Voltage
Phase
Frequency
Wire size
Interconnection
Voltage
cable
Wire size
Recommended field fuse
Earth leakage circuit breaker/
residual current circuit breaker
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values.
Please use the table above to specify the requirements for the power supply
wiring.
NOTICE
When using residual current operated circuit breakers, be sure to use a high-speed
type 300 mA rated residual operating current.
RXYSA8
(a)
18.5 A
Must comply with national wiring regulation.
Wire size based on the current, but not less
2.5 mm²
Only use harmonised wire providing double
insulation and suitable for applicable voltage.
2-core shielded cable
Must comply with national wiring regulation.
20
Electrical installation
|
Outdoor unit
RXYSA10
RXYSA12
22 A
380-415 / 400 V
3N~
50/60 Hz
5 core cable
than:
4 mm²
220-240 V
0.75-1.5 mm²
25 A
Installer and user reference guide
24 A
32 A
123