Page 1
Installation and operation manual VRV 5 safety valve unit SV1A25AJV1B SV4A14AJV1B Installation and operation manual SV6A14AJV1B English VRV 5 safety valve unit SV8A14AJV1B...
Page 2
Lowest underground floor All other floors No safety measure No safety measure Ventilated enclosure Ventilated enclosure External alarm + natural ventilation m [kg] m [kg] [m²] [m²] m [kg] Lowest underground floor All other floors m [kg] Lowest underground floor All other floors No safety measure External alarm OR...
23 Glossary 13.3.2 To open the unit ............25 13.3.3 To close the unit............25 13.4 Mounting the unit............... 25 13.4.1 To mount the unit ............25 SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
If the metal duct passes through a metal lath, wire lath or Daikin website (publicly accessible). metal plate of the wooden structure, separate the duct and ▪ The full set of the latest technical data is available on the Daikin wall electrically. Business Portal (authentication required).
Page 5
When performing the test operation, NOT ONLY the outdoor unit, but the connected indoor unit will operate as well. Working on an indoor unit while performing a test operation is dangerous. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
4 13]. requirements for R32 WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed ONLY by authorised persons. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 –...
Contact your dealer. ▪ Do NOT sit, climb or stand on the unit. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 8
▪ Do NOT use the unit until a service break down or cause a fire. person confirms that the part from which the refrigerant leaked has been repaired. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
WARNING Make sure installation, servicing, maintenance, repair and applied materials follow the instructions from Daikin (including all documents listed in “Documentation set”) and, in addition, comply with applicable legislation and are performed by qualified persons SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 –...
"CH-23" after the end of the sensor lifetime. For more information, see the reference guide of the user interface and contact your dealer. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Contact your installer. State the symptoms, the complete model name of the unit (with manufacturing number if possible) and the installation date (possibly listed on the warranty card). SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
VRV direct expansion (DX) indoor unit Insulation tube for stopper pipe Ø15.9 mm (4× for SV4A, VRV direct expansion (DX) indoor unit (direct connection 2× for SV1A and SV6~8A) from outdoor to indoor) Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
12.2 System layout requirements 11.4.1 Possible options for the SV unit The VRV 5 heat pump uses R32 refrigerant, which is rated as A2L and is mildly flammable. INFORMATION To comply with the requirements of enhanced tightness refrigerating All possible options are mentioned in the option list below.
External alarm + Natural ventilation Natural ventilation Note: The flowchart is an overview. Always refer to the full text mentioned in this manual for clear understanding and detailed explanation. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
(23.6 kg), which means that the safety measure can be cannot act as an ignition source during normal applied. operation. This requirement is met if the fan motor has an IP4X rating or better. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 18
SV unit 38.3 manufacturer. Duct “ Use the airflow rate and the sum of the pressure drops to select a Bend “ suitable fan. Duct “ Bend “ Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 19
"15.6 To connect the external cluster) of each outdoor unit system. is not allowed to have SV units in the same series cluster that belong to different outdoor unit systems. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 20
Before SV unit operation, it is required to perform a test run that run" [ 4 41] for simulates a refrigerant leak. See "17.2 SV unit test more details. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Installation SV unit(s) is completed Note: The flowchart is an overview. Always refer to the full text mentioned in this manual for clear understanding and detailed explanation. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Before SV unit operation, it is required to perform a test run that run" [ 4 41] for simulates a refrigerant leak. See "17.2 SV unit test more details. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit: ▪ In places where voltage fluctuates a lot. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
▪ For new ceilings, use sunken inserts, sunken anchors or other field supplied parts. ▪ Ceiling openings. Respect the following sizes and positions for the ceiling openings: B’ 450×450 [mm] Ceiling opening size: 800 mm (SV1~4A) 1200 mm (SV6~8A) Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
3 Tighten the metal clamp and bend the tip of the metal clamp so that the large, self-adhesive sealing pad (accessory) will not be Drain piping (field supply) forced outwards when applied. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
3 Insulate the ducting with field supply thermal insulation and with the accessory sealing material (against condensation drops). 2 Install the duct closing plate (accessory) using the same 4 screws. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
▪ Carefully guide the wires from the inside to the outside through the small hole in the unit's metal plate. Take care not to damage the connector and the earth wire connection. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 29
▪ Position the wire fixing plate over the screws and slide it in place. Make sure the backside is aligned properly with the insulation of the switch box, in order to make it airtight. ▪ Tighten the two screws. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
3 Close the SV unit. See "13.3.3 To close the Piping installation CAUTION instructions" [ 4 4] to make "2 Specific installer safety sure this installation complies with all safety regulations. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Maximum number of ports of SV units in Ambient Humidity Minimum thickness refrigerant flow-through (c) temperature Maximum number of indoor units connected to ≤30°C 75% to 80% RH 15 mm SV units in refrigerant flow-through (c) SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Always use tape (field supply) to prevent air gaps in the seam between the insulation tubes. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
"Guidelines when connecting the electrical wiring" in the installer reference guide. Field wiring consists of: ▪ power supply wiring (including earth), ▪ DIII interconnection wiring between units. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
SV unit are connected to the terminals F1/F2 (Outdoor unit) Allowed on terminal block X2M on the (n+1) SV unit. NOT allowed For earth connections, use the following method: Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 35
Indoor unit A connected to the branch pipe A of SV unit 1 lower the switch box. and SV unit 2 respectively B1/B2 Indoor units B1 and B2 connected to the same branch pipe B of SV unit 1 SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
R32 sensor in the SV unit. The FAN output must be used when a ventilated enclosure is required (see "12.3 To determine required safety measures" [ 4 14]). Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Relay value is possible. External alarm power supply External alarm In general, normal operation can be resumed without special intervention after changing field settings. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Turn ON the power 6 hours before operation in order to situation (normal operation). have power running to the crankcase heater and to protect the compressor. 2 Push BS1 one time. Result: Mode 1 is accessed: Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Set ONLY on the LEFTMOST main PCB (A1P) of the SV unit. 8 Push BS1 one time to quit mode 2. [2-4] Setting to enable or disable all SV unit safety measures. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Page 40
Address for supervisor remote controller Main PCB Address value (e) HEX format) SV8A Set ONLY on the LEFTMOST main PCB (A1P) of the SV unit. SV6A SV4A Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
17.2.1 About the SV unit test run commissioning checklist is also available on the Daikin Business Portal (authentication required). The SV unit test run has to be performed on all SV units in the system, before the test run of the outdoor unit.
When a ventilated enclosure is required, the following requirements apply: ▪ pressure inside the SV unit has to be more than 20 Pa below the ambient pressure, ▪ minimum airflow rate: Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 – 2023.09...
Check if all field settings are made correctly. When in parallel or series configuration, the field settings of all SV units in a cluster need to be made correctly. SV1A25AJV1B+SV4~8A14AJV1B Installation and operation manual VRV 5 safety valve unit 4P709466-1 – 2023.09...
Before starting the maintenance and service, field setting must be their values to a value other than the factory default applied on the VRV 5 heat pump outdoor unit. For more information, setting. If you are unable to find the cause of the see the installation and operation manual of the outdoor unit.
▪ A subset of the latest technical data is available on the regional HIGH VOLTAGE High voltage Daikin website (publicly accessible). Intelligent eye sensor ▪ The full set of the latest technical data is available on the Daikin IPM* Intelligent power module Business Portal (authentication required). Contact...
Model DS1, DS2 factory settings Field supply SV1A Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation. Installation and operation manual SV1A25AJV1B+SV4~8A14AJV1B VRV 5 safety valve unit 4P709466-1 –...
Page 48
4P709466-1 0000000U 4P709466-1 2023.09 Verantwortung für Energie und Umwelt...