17 Unit installation
In this chapter
17.1 Preparing the installation site
17.1.1 Installation site requirements of the outdoor unit
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1A - 2020.07
WARNING
The installation MUST comply with the requirements that apply to this R32
equipment. For more information, see
4
refrigerant" [
17.1
Preparing the installation site ................................................................................................................................................
17.1.1
17.1.2
17.2
Opening and closing the unit .................................................................................................................................................
17.2.1
About opening the units ........................................................................................................................................
17.2.2
To open the outdoor unit ......................................................................................................................................
17.2.3
To close the outdoor unit.......................................................................................................................................
17.3
Mounting the outdoor unit ....................................................................................................................................................
17.3.1
17.3.2
17.3.3
17.3.4
To install the outdoor unit .....................................................................................................................................
17.3.5
To provide drainage ...............................................................................................................................................
17.3.6
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
WARNING
The appliance shall be stored in a room without continuously operating ignition
sources (example: open flames, an operating gas appliance or an operating electric
heater).
INFORMATION
Also read the following requirements:
▪
General installation site requirements. See the "General safety precautions"
chapter.
▪
Service space requirements. See the "Technical data" chapter.
▪
Refrigerant piping requirements (length, height difference). See further in this
"Preparation" chapter.
CAUTION
Appliance NOT accessible to the general public, install it in a secured area, protected
from easy access.
This unit is suitable for installation in a commercial and light industrial environment.
"3.1 Instructions for equipment using R32
17].
17
Unit installation
|
Installer and user reference guide
67
67
70
71
71
71
71
73
73
73
73
74
74
75
67