APPENDIX 2 (VENTILATION GUIDENCE)
Ventilation Requirements for "Murelle Equipe 220 – 660 ErP" Cascade
This information is provided for guidance only
BS6644:2005 requires the temperatures in the room or compartment not to exceed certain levels:
25°C up to 100 mm from floor level
32°C 1500 mm above floor level
40°C 100 mm from ceiling level
The following provided for guidance only, and assumes the ventilation air is taken directly from outside. The size of the
vents may need to be increased in respect of other appliances installed in the same area, and seasonal use. Take care
that the position of low level vents would not be subject to adverse weather conditions, i.e. flooding.
When installed as a class B appliance (opened flue, not room sealed).
Installed in a room
High level, within 15% of room height from the ceiling = 2 cm
Low Level, low as possible within G20 - 1000 mm G31 - 250 mm = 4 cm
Each model requirement for their net heat input is:
Murelle Equipe Cascade
220 ErP high
436 cm
330 ErP high
648 cm
440 ErP high
846 cm
550 ErP high
1080 cm
660 ErP high
1296 cm
Installed in a compartment or enclosure
High level, within 15% of room height from the ceiling = 5 cm
Low Level, low as possible within G20 - 1000 mm G31 - 250 mm = 10 cm
Each model requirement for their net heat input is:
Murelle Equipe Cascade
220 ErP high
1090 cm
330 ErP high
1620 cm
440 ErP high
2160 cm
550 ErP high
2700 cm
660 ErP high
3240 cm
When installed as a class C appliance (room sealed)
Installed in a room
High level, within 15% of room height from the ceiling = 2 cm
Low Level, low as possible within G20 - 1000 mm G31 - 250 mm = 2 cm
Each model requirement for their net heat input is:
Murelle Equipe Cascade
220 ErP high
436 cm
330 ErP high
648 cm
440 ErP high
846 cm
550 ErP high
1080 cm
660 ErP high
1296 cm
Installed in a compartment or enclosure
High level, within 15% of room height from the ceiling = 5 cm
Low Level, low as possible within G20 - 1000 mm G31 - 250 mm = 5 cm
Each model requirement for their net heat input is:
Murelle Equipe Cascade
220 ErP high
1090 cm
330 ErP high
1620 cm
440 ErP high
2160 cm
550 ErP high
2700 cm
660 ErP high
3240 cm
2
low
872 cm
2
2
low
1296 cm
2
low
1728 cm
2
low
2160 cm
2
low
2592 cm
2
2
low
2180 cm
2
low
3240 cm
2
low
4320 cm
2
low
5400 cm
2
low
6480 cm
2
2
low
436 cm
2
2
low
648 cm
2
2
low
846 cm
2
2
low
1080 cm
2
low
1296 cm
2
2
low
1090 cm
2
low
1620 cm
2
low
2160 cm
2
low
2700 cm
2
low
3240 cm
2
per Kw net heat input (Nominal)
per Kw net heat input (Nominal)
2
2
2
2
2
per Kw net heat input (Nominal)
per Kw net heat input (Nominal)
2
2
2
2
2
2
per Kw net heat input (Nominal)
per Kw net heat input (Nominal)
2
2
2
per Kw net heat input (Nominal)
per Kw net heat input (Nominal)
2
2
2
2
2
2
47