8.4 Checking the heat pump performance

To check the correct functioning of the heat pump, position the sensors in the points indicated and compare
the graphs with those provided below.
In the event of significant variations, the presence of a fault is likely.

8.4.1 Models without auxiliary capacitor HP A-50%

1 Capacitor inlet
2 Capacitor outlet
100
80
60
40
20
0
10
20
30
1
601
1201
1801
-20
Time in minutes
-40
Technical Support - A.D.L.
40
50
60
70
2401
3001
3601
4201
1
3 Evaporator inlet
4 Evaporator outlet
80
90
100
110
4801
5401
6001
6601
1
2
3
4
2
3
60/66
120
130
140
150
7201
7801
8401
9001
4
599 74 32-54 Rev.01
160
170
180
9601
10201 10801