Connection Diagram - 3 Relays - Fronius Primo GEN24 208-240 Operating Instructions Manual

Hide thumbs Also See for Primo GEN24 208-240:
Table of Contents

Advertisement

Connection dia-
The ripple control signal receiver and the I/O terminal of the inverter can be con-
gram - 3 relays
nected to one another as shown in the connection diagram.
For distances of over 11 yd between the inverter and the ripple control signal re-
ceiver, a CAT 5 cable is recommended as a minimum and the shielding must be
connected on one side at the push-in terminal of the data communication area
(SHIELD).
(1)
(2)
Use pre-configured file for 3-relay operation:
1
2
3
The settings for 3-relay operation are saved.
(1)
60 %
30 %
0 %
Ripple control signal receiver with 3 relays for effective power limitation.
I/Os of the data communication area.
Download the file (.fpc) under
Upload the file (.fpc) in the
"Import"
the
button.
Click "Save".
V+
IN8
IN9
IN10
3-relay operation
to the mobile device.
"I/O power management"
(2)
menu field by clicking
91