Fronius Primo GEN24 208-240 Operating Instructions Manual page 69

Hide thumbs Also See for Primo GEN24 208-240:
Table of Contents

Advertisement

The network wizard and product setup can be performed independently. A net-
work connection is required for the Solar.web installation wizard.
Ethernet:
Establish a connection to the inverter (LAN1) using a network cable (min.
1
CAT5 STP).
2
Open the access point by touching the sensor once
Communications LED flashes blue.
ü
Enter the IP address 169.254.0.180 in the address bar of the browser and
3
confirm. The installation wizard opens.
Follow the installation wizard and complete the installation in the individual
4
areas.
Add the system components in Solar.web and commission the PV system.
5
The network wizard and product setup can be performed independently. A net-
work connection is required for the Solar.web installation wizard.
1
open access point
192.168.250.180
2
69