Feed-In Limit - Fronius Primo GEN24 208-240 Operating Instructions Manual

Hide thumbs Also See for Primo GEN24 208-240:
Table of Contents

Advertisement

5
6
7
Risk due to unauthorised access.
Incorrectly set parameters can negatively influence the public grid and/or the in-
verter feeding energy into the grid, and lead to a loss of conformity with the
standard.

Feed-in limit

Energy companies or grid operators can prescribe feed-in limits for an inverter
(e.g., max. 70% of the kWp or max. 5 kW).
The feed-in limit takes account of self-consumption in the household before the
power of an inverter is reduced:
-
-
The feed-in limit only becomes active if the power of feeding in is higher than the
set power reduction.
"Off"
The inverter converts all available PV energy and feeds it into the public grid.
"Limit for the entire system"
The entire PV system is limited to a fixed power limit. A value must be set for the
permissible total power of feeding in.
"Total DC power of the system"
Input field for the total DC power of the system in Wp.
This value is used if the
system"
"Hard limit"
If this value is exceeded, the inverter switches off within max. 5 seconds. This
value must be higher than the value set for
"Soft limit"
If this value is exceeded, the inverter readjusts down to the set value within the
time required by the national standards and regulations.
"Maximum permitted power of feeding in of the entire system"
Input field for the "Maximum permitted power of feeding in of the entire system"
in W or % (setting range: -10 to 100%).
If there is no meter in the system or if a meter has failed, the inverter limits the
power of feeding in to the set value.
A contract page appears on which the request for the access code to change
the grid parameters for Fronius inverters is located
Accept the Terms of use by checking
of use
and click
Confirm & Save
After that, the codes can be retrieved in the drop-down menu at the top right
under
Show inverter codes
CAUTION!
The parameters may only be adjusted by installers/service technicians from
authorised specialist companies.
Do not give the access code to third parties and/or unauthorised persons.
An individual limit can be set.
A Fronius Smart Meter can be connected to the Modbus push-in terminal of
the data communication area, at the terminals M0/M1- / M0/M1+ for Mod-
bus data.
"Maximum permitted power of feeding in of the entire
is specified in %.
Yes, I have read and agree to the terms
"Soft