Ground electrode terminal (6-pin)
Select a sufficiently large cable cross-section based on the actual device output.
AWG 14–6 /
2
2.5 - 16 mm²
AWG 14–8 /
4
2.5 - 10 mm²
*
Cable diameter
Cable diameter for connection to the push-in terminal: 0.27 inches
for push-in ter-
minals
IMPORTANT
For double-insulated cables with a cable diameter above 0.27 inches, the outer
layer of insulation must be removed for the connection to the push-in terminal.
Permitted cables
Cables with the following design can be connected to the terminals of the invert-
for the data
er:
communication
-
connection
-
IMPORTANT!
If several single conductors are connected to an input of the push-in terminals,
connect the single conductors with a corresponding ferrule.
WSD connections with push-in terminal
Dis-
Strip-
tance
ping
max.
length
109 yd
0.39 inch
/ 100
es / 10
m
mm
Modbus connections with push-in terminal
Dis-
Strip-
tance
ping
max.
length
328 yd
0.39 inch
/ 300
es / 10
m
mm
46
AWG 14–6 /
2.5 - 16 mm²
AWG 14–8 /
2.5 - 10 mm²
According to product standards UL1741 3rd Edition, Table 20.1 and CSA-
C22.2 No.107.1-16
Copper: round, solid
Copper: round, fine-stranded
AWG 26–16
AWG 26–16
AWG 26–16
AWG 26–16
AWG 14–6 /
AWG 14–6 /
2.5 - 16 mm²
2.5 - 16 mm²
AWG 14–8 /
AWG 14–8 /
2.5 - 10 mm²
2.5 - 10 mm²
AWG 26–18
AWG 26–16
AWG 26–18
AWG 26–16
AWG 14–6 /
2.5 - 16 mm²
AWG 14–8 /
2.5 - 10 mm²
Cable re-
commenda-
tion
min. CAT 5
UTP (un-
shielded
twisted pair)
Cable re-
commenda-
tion
min. CAT 5
STP (shiel-
ded twisted
pair)