Insert the conduit into the knockout and fasten it using the torque specified
4
by the manufacturer. Seal the conduit as per the chapter headed
knockouts for connection
5
6
Drill out the knockout with a step drill.
on page 41.
Guide the mains cable through the
conduit from below.
Remove the OP terminal.
Strip the insulation of the single con-
ductors by 0.47 inches / 12 mm.
The cable cross-section must be
between AWG 16 and AWG 8. Lift to
open the terminal's operating lever and
insert the stripped single conductor in-
to the slot provided, all the way up to
the stop. Then close the operating
lever until it engages.
NOTE!
Only one conductor may be connected
to each pin. The lines can be connec-
ted without ferrules.
Preparing
61