3.10 AUTOMATIC CALIBRATION FUNCTION (TA)

This function allows you to calibrate the appliance automatically without the possibility of altering the parameters. "Automatic calibra-
tion" is used after the parameters have been changed or the components have been replaced (Parag. 3.9).
Before carrying out automatic calibration, ensure that all the requirements indicated in (Parag. 1.29 - 1.30).
In the event of anomaly "62" or "72" (Parag. 2.5) :in these cases, automatic calibration is required
If you want to dissipate the entire energy on domestic hot water, set the DHW set to maximum. Then activate the "automatic calibration"
function and open a hot water tap.
The function can be activated from the Special Functions menu by selecting "tA".
If OFF or Stand-by mode is selected, the function cannot be activated.
RESET
RESET
INFO
RESET
INFO
MODE
MODE
INFO
MODE
To access the automatic calibration function, the "INFO" button
must be pressed and held down for longer than 5 seconds; two sin-
gle flashing "-" dashes appear on the display and the password (
) for access to the programming menus must be entered.
61
To enter the left digit use the knob (5) for adjusting the domestic
hot water temperature (
(6) for adjusting the central heating temperature (
Press MODE to confirm the password.
62
Once in the menu, press INFO until the flashing "tA" appears.
Confirm by pressing MODE.
63
), to enter the right digit use the knob
).
93