3.9

COMPLETE CALIBRATION FUNCTION

Before carrying out complete calibration, ensure that all
the requirements indicated in the relevant paragraphs
have been met (Par. 1.25 e 1.26).
To access this function it is crucial that there are no active requests
for central heating or DHW production and that the boiler is not
in "Stand-by" mode.
In the event of anomaly "62" or "72" (Par. 2.5) the boiler cancels
any requests by itself.
During the various calibration stages, the CO
checked and possibly corrected as described in (Par. 3.10).
The energy produced is dissipated via the heating circuit; alterna-
tively, the energy can be released from the DHW circuit by open-
ing any hot water tap.
In this case the only active temperature control is the
flow probe that limits the maximum temperature exit-
ing the boiler at 90°C, therefore be careful not to get
burned.
The calibration procedure involves various stages:
- nominal heat output calibration;
- intermediate heat output ignition calibration;
- minimum heat output calibration;
- calibration self-check.
Each calibration procedure, if carried out without altering the
parameters, lasts 5 minutes at the most, after which it switches au-
tomatically to the next parameter until the calibration process is
complete.
Once activated, to cancel the complete calibration func-
tion, press the button (
the power supply. The adjustments present before acti-
vating the function will be maintained.
value can be
2
) for 2 seconds or disconnect
Complete calibration activation procedure.
Nominal heat
output: with the function active, the boiler carries out the proce-
dures required to calibrate the appliance at the nominal heat out-
put.
At this stage the display features flashing icons: "
and the operating temperature alternated with the current oper-
ating heat output (99%) is displayed; once the parameters are de-
tected and stabilised, the "
may take a few minutes), meaning that the nominal heat output
settings have been set.
Press and hold buttons "
and "
" for more than 5 sec-
onds.
42
The display will show two dash-
es "--" flashing. Now enter the
password "62" to activate the
complete calibration (enter the
first digit by pressing the 1-2
buttons (
) and the second
43
digit by pressing the buttons
5-6 (
).
Press the "
" key to activate
calibration.
Once activated, the complete
calibration function has four
phases:
44
" and "
" symbol will start flashing (this
Only after the "
flashes is it possible to change
the CO
value (Par. 3.10) or
2
switch to the next heat output
parameter by pressing the "
button.
45
"
"
" symbol
"
57